2022-08-25 12:40:15 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22071245 |
| |
| 1- RESUBMIT SHUTTERS FLORIDA PRODUCT APPROVAL. |
| INFORMATION IS NOT LEGIBLE. THE SPAN SCHEDULES AND |
| ANCHOR SCHEDULES ARE VERY BLURRY AND ARE NOT LEGIBLE. |
| SUBMIT CLEAR AND LEGIBLE INFORMATION. AND PLEASE UPLOAD |
| DRAWINGS ON LANDSCAPE ORIENTATION NOT ON VERTICAL |
| ORIENTATION. SEC. 107.2.1.3 CITY AMENDMENTS. |
| |
| 2- REVISE SHUTTERS INSTALLATION SCHEDULE: |
| A)SHUTTERS MOUNTING CONDITIONS AND ANCHOR CONNECTION |
| TYPE IS NOT CLEAR. NONE OF THE MOUNTING CONDITIONS |
| CIRCLED ON SHEETS 5 AND 6 SHOW CONNECTION TYPE C5 AS |
| SPECIFIED ON THE SHUTTERS INSTALLATION SCHEDULE. REVISE |
| AS REQUIRED TO REFLECT PROPOSED MOUNTING INSTALLATION |
| AND ANCHOR CONNECTION TYPE. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| NOTE: TRENCH INSTALLATION DOESN'T INCLUDE ANCHOR |
| CONNECTION TYPE C5. |
| |
| B)SHUTTER MOUNTING INSTALLATION AND ANCHOR CONNECTION |
| TYPE COLUMN ONLY SPECIFY C5 FOR ALL PROPOSED MOUNTING |
| CONDITIONS. CONNECTION TYPE C5 DOESN'T APPLY TO ALL |
| PROPOSED MOUNTING CONDITION. REVISE AS REQUIRED AND |
| CLEARLY IDENTIFY THE PROPOSED MOUNTING CONDITION. |
| COORDINATE WITH ITEM #2 ABOVE. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| C) SHUTTER SPAN IS INCORRECT. SHUTTER SPAN IS THE |
| OPENING HEIGHT NOT THE WIDTH. REVISE AS REQUIRED. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| D) EDGE DISTANCE IS INCORRECT. SEE HIGHLIGHTED ANCHOR |
| SCHEDULE AND REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| NOTE: COORDINATE WITH ITEM #1(F) BELOW. |
| |
| E) ANCHOR SPACING NEEDS TO BE COORDINATED WITH ANCHOR |
| SCHEDULE TABLE USED DEPENDING ON THE SUBSTRATE TYPE |
| (CONCRETE OR HOLLOW CONCRETE BLOCK). REVISE AS |
| REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| NOTE: COORDINATE WITH ITEM #3(F) BELOW. |
| |
| F)REVISE INFORMATION SUBSTRATE COLUMN. TYPICALLY THE |
| BOTTOM OF WINDOW OPENINGS IS CONCRETE BLOCK. REVISE |
| INSTALLATION SCHEDULE USING THE ANCHOR FOR CONCRETE |
| BLOCK SUBSTRATE OR PROVIDE PROOF SHOWING BOTTOM OF |
| OPENINGS HAS POURED CONCRETE WITH THE STRENGTH |
| SPECIFIED ON ANCHOR SCHEDULE. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |