2022-08-25 12:40:15RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22071245
  
 1- RESUBMIT SHUTTERS FLORIDA PRODUCT APPROVAL.
 INFORMATION IS NOT LEGIBLE. THE SPAN SCHEDULES AND
 ANCHOR SCHEDULES ARE VERY BLURRY AND ARE NOT LEGIBLE.
 SUBMIT CLEAR AND LEGIBLE INFORMATION. AND PLEASE UPLOAD
 DRAWINGS ON LANDSCAPE ORIENTATION NOT ON VERTICAL
 ORIENTATION. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 2- REVISE SHUTTERS INSTALLATION SCHEDULE:
 A)SHUTTERS MOUNTING CONDITIONS AND ANCHOR CONNECTION
 TYPE IS NOT CLEAR. NONE OF THE MOUNTING CONDITIONS
 CIRCLED ON SHEETS 5 AND 6 SHOW CONNECTION TYPE C5 AS
 SPECIFIED ON THE SHUTTERS INSTALLATION SCHEDULE. REVISE
 AS REQUIRED TO REFLECT PROPOSED MOUNTING INSTALLATION
 AND ANCHOR CONNECTION TYPE. SEC. 107.2.1 CITY
 AMENDMENTS.
 NOTE: TRENCH INSTALLATION DOESN'T INCLUDE ANCHOR
 CONNECTION TYPE C5.
  
 B)SHUTTER MOUNTING INSTALLATION AND ANCHOR CONNECTION
 TYPE COLUMN ONLY SPECIFY C5 FOR ALL PROPOSED MOUNTING
 CONDITIONS. CONNECTION TYPE C5 DOESN'T APPLY TO ALL
 PROPOSED MOUNTING CONDITION. REVISE AS REQUIRED AND
 CLEARLY IDENTIFY THE PROPOSED MOUNTING CONDITION.
 COORDINATE WITH ITEM #2 ABOVE.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 C) SHUTTER SPAN IS INCORRECT. SHUTTER SPAN IS THE
 OPENING HEIGHT NOT THE WIDTH. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 D) EDGE DISTANCE IS INCORRECT. SEE HIGHLIGHTED ANCHOR
 SCHEDULE AND REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
 NOTE: COORDINATE WITH ITEM #1(F) BELOW.
  
 E) ANCHOR SPACING NEEDS TO BE COORDINATED WITH ANCHOR
 SCHEDULE TABLE USED DEPENDING ON THE SUBSTRATE TYPE
 (CONCRETE OR HOLLOW CONCRETE BLOCK). REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: COORDINATE WITH ITEM #3(F) BELOW.
  
 F)REVISE INFORMATION SUBSTRATE COLUMN. TYPICALLY THE
 BOTTOM OF WINDOW OPENINGS IS CONCRETE BLOCK. REVISE
 INSTALLATION SCHEDULE USING THE ANCHOR FOR CONCRETE
 BLOCK SUBSTRATE OR PROVIDE PROOF SHOWING BOTTOM OF
 OPENINGS HAS POURED CONCRETE WITH THE STRENGTH
 SPECIFIED ON ANCHOR SCHEDULE. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,