Plan Review Notes For Permit 22071212 |
Permit Number |
22071212 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-08-04 11:56:31 | ***PRIOR COMMENTS ADDRESSED BY CONTRACTOR, FIRE PLAN | | REVIEW STATUS CHANGED TO PASS*** | | | | SPRINKLER COVERAGE ADEQUATE FOR ARE LISTED AS "FOUNDER | | LOUNGE", SPRINKLERS POSITIONED TO PROVIDE COVERAGE | | BELOW CEILING ARCHETECTURAL FEATURE. | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | INSPECTIONS AND APPROVAL. | | | | LT. BRIAN DOLAN | | DIVISION OF FIRE PREVENTION | | 561-804-4752 | | [email protected] | | | 2022-08-02 12:10:26 | THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN | | DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH | | FIRE RESCUE. | | | | DOES PLACEMENT OF SPRINKLERS IN MARKED AREA PROVIDE | | ADEQUATE COVERAGE FOR ENTIRE SPACE? | | DENSITY OF COVERAGE IS LOWER THAN OTHER AREAS IN PLAN | | SET WITH SAME HEAD TYPE. | | | | ALL WORK ON THE UNDERGROUND FIRE MAIN IS REQUIRED TO BE | | COMPLETED BY A CERTIFIED UNDERGROUND CONTRACTOR AND | | SHALL COMPLY WITH NFPA 24 STANDARD FOR THE INSTALLATION | | OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES. | | SEPARATE SHOP DRAWINGS COMPLIANT WITH 61G15-32.004 | | DESIGN OF WATER BASED FIRE PROTECTION SYSTEMS ARE | | REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE | | FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM. | | | | LT. BRIAN DOLAN | | DIVISION OF FIRE PREVENTION | | 561-804-4752 | | [email protected] | | | | | | |
|