2022-07-28 12:29:47 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 22071210 733 NEW YORK ST |
| MASTER PERMIT 21100899 |
| |
| 1ST REVIEW |
| GAS COMMENTS: DENIED |
| |
| SEPARATE PERMITS SHALL BE REQUIRED FOR CONNECTION TO |
| GAS APPLIANCES LISTED AS FUTURE. |
| |
| 1.MASTER PERMIT 21100899 DOES NOT INDICATE ANY OF THE |
| APPLIANCES OR EQUIPMENT NOTED IN THIS PERMIT |
| APPLICATION. PER WPB FBC 107.2.1, PROVIDE BACKUP FROM |
| MASTER PERMIT. |
| |
| 2.PER WPB FBC 107.2.1, PROVIDE, ON THE RISER DIAGRAM, |
| LOCATIONS OF ALL SHUTOFF VALVES. |
| |
| 3. PER WPB FBC 107.2.1, PROVIDE SITE PLAN WITH |
| LOCATIONS OF SERVICE METER/REGULATOR, FUTURE GENERATOR |
| AND FUTURE POOL HEATER. |
| |
| 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| SPECIFICATION SHEETS / INSTALLATION MANUAL (FBC |
| FG402.2, 301.3 /FBC RES G2404.3) FOR ALL GAS EQUIPMENT |
| AS FOLLOWS: |
| ***A) TANKLESS WATER HEATER |
| ***B) DRYER(S) |
| ***C) RANGE |
| |
| 5. THE INSTALLATION MANUALS FOR ALL GAS APPLIANCES / |
| EQUIPMENT SHALL BE ONSITE AT THE TIME OF INSPECTION. |
| FBC FG 305.1, FBC RES G2408.1. |
| |
| 6.PER WPB FBC 107.2.1, PROVIDE SIZES, LENGTHS AND |
| MATERIAL FOR EACH PIPE SEGMENT BETWEEN THE SERVICE |
| METER/REGULATOR AND THE BRANCH SERVING THE FUTURE |
| FIREPLACE. |
| |
| 7.PER WPB FBC 107.2.1, PROVIDE SIZING TABLE FOR |
| SCHEDULE 40 STEEL PIPING BETWEEN THE SERVICE |
| METER/REGULATOR AND THE 11 INCH WC REGULATOR. |
| |
| 8. PLEASE RECALCULATE THE LONGEST RUN FROM THE 11 INCH |
| WC REGULATOR TO MOST REMOTE APPLIANCE IN THE LESS THAN |
| 2 PSI SYSTEM. PLEASE NOTE, THERE CAN ONLY BE ONE (1) |
| LONGEST RUN IN ANY SYSTEM. |
| |
| 9.PER WPB FBC 107.2.1, PROVIDE A CHART LISTING ALL |
| APPLIANCES AND QUANTITY WITH BTU VALUE AND TOTAL BTU |
| LOAD. NOTE TOTAL BTU LOAD FOR THE 2 PSI SYSTEM (WHICH |
| INCLUDES TOTAL DOWNSTREAM OF THE 11 INCH WC REGULATOR |
| AND THE TOTAL LOAD FOR THE LESS THAN 2 PSI SYSTEM. |
| |
| 10. PER WPB FBC 107.2.1, PROVIDE, ON THE RISER DIAGRAM, |
| EHD SIZE(S) OF CSST SEGMENTS TO CORRESPOND WITH |
| SUPPLIED FBC FG TABLE 402.4 (15) |
| |
| 11.PER WPB FBC 107.2.1, LIST THE TABLE(S) USED FOR |
| CALCULATING PIPE SIZES. |
| |
| 12.PER WPB FBC 107.2.1, IDENTIFY OR CLEARLY SHOW THE |
| SHUTOFF VALVE AHEAD OF THE 11 INCH WC REGULATOR. FBC FG |
| 409.4, FBC RES G 2420.4 |
| |
| 14.PER WPB FBC 107.2.1, SUBMIT CALCULATIONS FOR |
| COMBUSTION AIR FOR THE RANGE AND DRYERS PER THE FBC FG |
| 304.1, 614.6 /FBC RES G 2407.1 AND G2439.4. PROVIDE |
| MAKEUP AIR FOR THE DRYERS IF REQUIRED. |
| |
| 15.PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| SPECIFICATION/INSTALLATION MANUAL AND DETAIL FOR |
| TANKLESS WATER HEATER COMBUSTION AIR AND EXHAUST VENT |
| SYSTEM(S). |
| |
| 16.PER WPB FBC 107.2.1, PROVIDE ON FLOOR PLAN, |
| LOCATIONS OF ALL APPLIANCES AND CORRESPONDING BTU |
| LOADS. |
| |
| 17. THE FUTURE GENERATOR WILL REQUIRE A SEPARATE |
| PERMIT. PLEASE NOTE THIS ON THE PLAN PER WPB FBC |
| 107.2.1. IT SHOULD BE NOTED THAT THE "FUTURE GENERATOR" |
| WILL NEED 10 FOOT SETBACKS FROM OPENINGS INTO THE |
| STRUCTURE. |
| |
| 18. THE FUTURE POOL HEATER WILL REQUIRE A SEPARATE |
| PERMIT. PLEASE NOTE THIS ON THE PLAN PER WPB FBC |
| 107.2.1. IT SHOULD BE NOTED THAT THE "FUTURE POOL |
| HEATER" WILL NEED 10 FOOT SETBACKS FROM OPENINGS INTO |
| THE STRUCTURE. |
| |
| 19. THE FUTURE FIREPLACE WILL REQUIRE A SEPARATE |
| PERMIT. PLEASE NOTE THIS ON THE PLAN PER WPB FBC |
| 107.2.1. |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |