Plan Review Notes
Plan Review Notes For Permit 22071177
Permit Number 22071177
Review Stop G
Sequence Number 2
Notes
Date Text
2022-08-03 07:55:592ND GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. NOT ADDRESSED - 2017 WPB AMEND - 107.3 - THE
 GENERATOR WILL REQUIRE A SEPARATE PERMIT. PLEASE MARK
 THIS AS A "FUTURE GENERATOR". IT SHOULD BE NOTED THAT
 THE "FUTURE GENERATOR" WILL NEED 10 FOOT SETBACKS FROM
 OPENINGS INTO THE STRUCTURE.
  
 2. NOT ADDRESSED - 2017 WPB AMEND 107.3.5.3 (13) - SHOW
 THE COMBUSTION AIR CALCS FOR THE DRYER INSTALLATION AND
 PROVIDE MAKEUP AIR IF REQUIRED.
  
 3. NOT ADDRESSED. THE POOL PERMIT INDICATES A HEAT
 PUMP. IN ORDER TO DO A GAS HEATER, A REVISION OR A
 SEPARATE PERMIT IS REQUIRED. -- 2017 WPB AMEND - 107.3
 - THE POOL HEATER WILL REQUIRED A SEPARATE PERMIT.
 PLEASE INDICATE ON PLANS.
  
 4. THE DRAWING SEEMS TO INDICATE THE WATER HEATER IS
 INDOORS AND THE SPECS SHOW AN OUTDOOR UNIT - CLARIFY
 THE DRAWING OR CHANGE THE SPECS. IF IT IS AN INDOOR
 UNIT, SHOW THE VENTING AND/OR COMBUSTION AIR CALCS.
 2017 WPB AMEND 107.3.5.3 (13) - SHOW THE LOCATION OF
 THE WATER HEATER ON A FLOOR PLAN AND, IF INDOORS, SHOW
 THE COMBUSTION AIR CALCS.
  
 5. DONE
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  