2022-08-03 07:55:59 | 2ND GAS REVIEW |
| |
| V7 FPC - 2020 FLORIDA PLUMBING CODE |
| V7 FGC - 2020 FLORIDA FUEL GAS |
| V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| 2021 F.S. - 2021 FLORIDA STATUTES |
| 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FBC CHAPTER 1 |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. NOT ADDRESSED - 2017 WPB AMEND - 107.3 - THE |
| GENERATOR WILL REQUIRE A SEPARATE PERMIT. PLEASE MARK |
| THIS AS A "FUTURE GENERATOR". IT SHOULD BE NOTED THAT |
| THE "FUTURE GENERATOR" WILL NEED 10 FOOT SETBACKS FROM |
| OPENINGS INTO THE STRUCTURE. |
| |
| 2. NOT ADDRESSED - 2017 WPB AMEND 107.3.5.3 (13) - SHOW |
| THE COMBUSTION AIR CALCS FOR THE DRYER INSTALLATION AND |
| PROVIDE MAKEUP AIR IF REQUIRED. |
| |
| 3. NOT ADDRESSED. THE POOL PERMIT INDICATES A HEAT |
| PUMP. IN ORDER TO DO A GAS HEATER, A REVISION OR A |
| SEPARATE PERMIT IS REQUIRED. -- 2017 WPB AMEND - 107.3 |
| - THE POOL HEATER WILL REQUIRED A SEPARATE PERMIT. |
| PLEASE INDICATE ON PLANS. |
| |
| 4. THE DRAWING SEEMS TO INDICATE THE WATER HEATER IS |
| INDOORS AND THE SPECS SHOW AN OUTDOOR UNIT - CLARIFY |
| THE DRAWING OR CHANGE THE SPECS. IF IT IS AN INDOOR |
| UNIT, SHOW THE VENTING AND/OR COMBUSTION AIR CALCS. |
| 2017 WPB AMEND 107.3.5.3 (13) - SHOW THE LOCATION OF |
| THE WATER HEATER ON A FLOOR PLAN AND, IF INDOORS, SHOW |
| THE COMBUSTION AIR CALCS. |
| |
| 5. DONE |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |