2022-07-28 08:53:42 | 1ST GAS REVIEW |
| |
| V7 FPC - 2020 FLORIDA PLUMBING CODE |
| V7 FGC - 2020 FLORIDA FUEL GAS |
| V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| 2021 F.S. - 2021 FLORIDA STATUTES |
| 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FBC CHAPTER 1 |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2017 WPB AMEND ? 107.3 - THE GENERATOR WILL REQUIRE |
| A SEPARATE PERMIT. PLEASE MARK THIS AS A "FUTURE |
| GENERATOR". IT SHOULD BE NOTED THAT THE "FUTURE |
| GENERATOR" WILL NEED 10 FOOT SETBACKS FROM OPENINGS |
| INTO THE STRUCTURE. |
| |
| 2. 2017 WPB AMEND 107.3.5.3 (13) - SHOW THE COMBUSTION |
| AIR CALCS FOR THE DRYER INSTALLATION AND PROVIDE MAKEUP |
| AIR IF REQUIRED. |
| |
| 3. 2017 WPB AMEND ? 107.3 - THE POOL HEATER WILL |
| REQUIRED A SEPARATE PERMIT. PLEASE INDICATE ON PLANS. |
| |
| 4. 2017 WPB AMEND 107.3.5.3 (13) - SHOW THE LOCATION OF |
| THE WATER HEATER ON A FLOOR PLAN AND, IF INDOORS, SHOW |
| THE COMBUSTION AIR CALCS. |
| |
| 5. 2017 WPB AMEND 107.3.5.3 (13) - PLEASE SHOW THE LINE |
| PRESSURES ON THE GAS LINE THAT YOU USED FOR SIZING THE |
| GAS PIPE. ALSO, INDICATE THE LENGHTS OR THE RUNS THAT |
| WERE USED FOR THE SIZING OF THE GAS LINE. |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |