2022-09-21 16:53:25 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 22071148 250 S AUSTRALIAN AVE FL 12 |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| APPROVAL. |
| |
| |
| 1. PER WPB FBC 107.2.1, PROVIDE A NOTE ON PLAN SHEETS |
| P-001, A101 AND A401 "REFER TO PLAN SHEETS G007, G008, |
| G009, G010, G011 AND G012 FOR ALL ACCESSIBILITY |
| REQUIREMENTS. IN CASE OF DISCREPENCY G007, G008, G009, |
| G010, G011 AND G012 REQUIREMENTS SHALL PREVAIL." FBC |
| ACC CHAPTERS 3 AND 6. |
| |
| |
| 2. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| SPECIFICATION/INSTALLATION MANUAL FOR THE WATER HEATER |
| ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY THE |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC |
| 107.2.1, 107.3.4. SUBMITTALS MAY BE DEFERRED IN |
| ACCORDANCE WITH SECTION WPB FBC 107.3.4.1. PROVIDE A |
| NOTE ON P-001 LISTING ANY DEFERRED SUBMITTALS. |
| |
| 3. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE |
| LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1. |
| PER WPB FBC 107.2.1, PROVIDE NOTE ON PLAN SHEET P-101 |
| STATING THE SAME. |
| |
| 4. PLAN SHEET P-101/PLUMBING SPECIFICATIONS: PER WPB |
| FBC 107.2.1, MAKE THE FOLLOWING CORRECTIONS. |
| ***A) NOTE 1-A; REPLACE "2017" WITH "2020" |
| ***B) NOTE 8-F (3); SOLDER SHALL BE LEAD FREE, NOT |
| TIN/ANTIMONY. FBC PL 605.2 AND 605.2.1 |
| ***C) NOTE 21-A; REPLACE "R" WITH "1/4 ". FBC PL 704.1 |
| |
| |
| 5. P-501/PLUMBING HEX NOTE EWH-1 AND EWH-2: PER WPB FBC |
| 107.2.1, PLEASE PROVIDE THE FOLLOWING; |
| ***A) NOTE COMPLIANCE WITH ASSE 1070; IF IT DOES NOT |
| COMPLY WITH ASSE 1070 THEN A THERMOSTATIC MIXING VALVE |
| FOR THE LAVATORIES COMPLYING WITH ASSE 1070 SHALL BE |
| PROVIDED PER FBC PL 419.5. |
| ***B) PROVIDE A DEDICATED VALVE IN THE COLD WATER |
| SUPPLY TO THE WATER HEATER PER FBC PL 503.1 |
| |
| 6. PER WPB FBC 107.2.1, 107.3.5.1.3 (3), FBC PL 601 AND |
| 604.3, PROVIDE CALCULATIONS FOR SIZING OF THE WATER |
| DISTRIBUTION SYSTEM. METHOD PROVIDED AS NOTED IN FBC PL |
| APPENDIX E, SECTION 103 IS AN APPROVED METHOD FOR |
| DETERMINING PIPE SIZE. |
| |
| 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3 (3), FBC PL 601 |
| AND 604.3, PROVIDE ON THE WATER RISER DIAGRAM SIZING OF |
| ALL SEGMENTS OF THE WATER DISTRIBUTION SYSTEM. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| |