Plan Review Notes
Plan Review Notes For Permit 22071147
Permit Number 22071147
Review Stop P
Sequence Number 1
Notes
Date Text
2022-11-21 14:34:51N/A
  
2022-09-27 15:53:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22071147 250 S AUSTRALIAN AVE FL 11
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
  
 1. PER WPB FBC 107.2.1, PROVIDE A NOTE ON PLAN SHEETS
 P-001, A101 AND A401 "REFER TO PLAN SHEETS G007, G008,
 G009, G010, G011 AND G012 FOR ALL ACCESSIBILITY
 REQUIREMENTS. IN CASE OF DISCREPENCY G007, G008, G009,
 G010, G011 AND G012 REQUIREMENTS SHALL PREVAIL." FBC
 ACC CHAPTERS 3 AND 6.
  
  
 2. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR THE WATER HEATER
 ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY THE
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC
 107.2.1, 107.3.4. SUBMITTALS MAY BE DEFERRED IN
 ACCORDANCE WITH SECTION WPB FBC 107.3.4.1. PROVIDE A
 NOTE ON P-001 LISTING ANY DEFERRED SUBMITTALS.
  
 3. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLAN SHEET P-101
 STATING THE SAME.
  
 4. PLAN SHEET P-101/PLUMBING SPECIFICATIONS: PER WPB
 FBC 107.2.1, MAKE THE FOLLOWING CORRECTIONS.
 ***A) NOTE 1-A; REPLACE "2017" WITH "2020"
 ***B) NOTE 8-F (3); SOLDER SHALL BE LEAD FREE, NOT
 TIN/ANTIMONY. FBC PL 605.2 AND 605.2.1
 ***C) NOTE 21-A; REPLACE "R" WITH "1/4 ". FBC PL 704.1
  
  
 5. P-501/PLUMBING HEX NOTE EWH-1 AND EWH-2: PER WPB FBC
 107.2.1, PLEASE PROVIDE THE FOLLOWING;
 ***A) NOTE COMPLIANCE WITH ASSE 1070; IF IT DOES NOT
 COMPLY WITH ASSE 1070 THEN A THERMOSTATIC MIXING VALVE
 FOR THE LAVATORIES COMPLYING WITH ASSE 1070 SHALL BE
 PROVIDED PER FBC PL 419.5.
 ***B) PROVIDE A DEDICATED VALVE IN THE COLD WATER
 SUPPLY TO THE WATER HEATER PER FBC PL 503.1
  
 6. PER WPB FBC 107.2.1, 107.3.5.1.3 (3), FBC PL 601 AND
 604.3, PROVIDE CALCULATIONS FOR SIZING OF THE WATER
 DISTRIBUTION SYSTEM. METHOD PROVIDED AS NOTED IN FBC PL
 APPENDIX E, SECTION 103 IS AN APPROVED METHOD FOR
 DETERMINING PIPE SIZE.
  
 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3 (3), FBC PL 601
 AND 604.3, PROVIDE ON THE WATER RISER DIAGRAM SIZING OF
 ALL SEGMENTS OF THE WATER DISTRIBUTION SYSTEM.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
  