Plan Review Notes For Permit 22071053 |
Permit Number |
22071053 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-07-29 13:56:01 | 1ST REVIEW FBC- 2020 RES. PLUMBING | | PERMIT- 22071053 | | 7/29/2022 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEETS 1 & 3: THE TDH CALCULATIONS INDICATE 35 FT. | | LENGTHS FOR SUCTION AND PRESSURE PIPING HOWEVER BASED | | ON THE POOL LAYOUT PLAN THE LENGTHS APPEAR GREATER THAN | | 35 FT.- PLEASE CORRECT- SECS. 4.4.9, 4.4.9.1 | | ANSI/APSP/ICC-7. | | | | 2) SHEET 3: PLEASE PROVIDE POOL EQUIPMENT ANCHORING | | DETAILS- TYPES AND SIZES OF ANCHOR BOLTS OR TAPCONS- | | SEC. R4501.22 FBC RES. | | | | 3) SHEET 5: REFER TO SEC. R4501.6.1 FBC RES AND SHOW | | THE CURRENT YEAR EDITIONS OF THE DESIGN STANDARDS IN | | EFFECT. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|