Plan Review Notes For Permit 22071053
Permit Number 22071053
Review Stop B
Sequence Number 1
Notes
Date Text
2022-08-26 11:55:40FBC-R4501.19 FINAL INSPECTION. FINAL ELECTRICAL AND
 BARRIER CODE INSPECTION SHALL BE COMPLETED PRIOR TO
 FILLING THE POOL WITH WATER.
 FBC-R403.10.3 COVERS. OUTDOOR HEATED SWIMMING POOLS AND
 OUTDOOR PERMANENT SPAS SHALL BE EQUIPPED WITH A
 VAPORRETARDANT COVER ON OR AT THE WATER SURFACE OR A
 LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS.
 EXCEPTION: WHERE MORE THAN 70 PERCENT OF THE ENERGY FOR
 HEATING, COMPUTED OVER AN OPERATION SEASON, IS FROM
 SITE-RECOVERED ENERGY, SUCH AS FROM A HEAT PUMP OR
 SOLAR ENERGY SOURCE, COVERS OR OTHER VAPOR-RETARDANT
 MEANS SHALL NOT BE REQUIRED.