Plan Review Notes
Plan Review Notes For Permit 22070987
Permit Number 22070987
Review Stop B
Sequence Number 1
Notes
Date Text
2022-08-18 07:25:39[email protected]
 [email protected]
  
 FBC 2020 RESIDENTIAL 301, SUBMITTED DESIGN PRESSURE
 REQUIREMENT FOR WNDOWS 2 AND 3, WITH MULLION, IS 49.3
 PSF. MULLION SUBMITTED IS TESTED FOR MDP 46.1 PSF.
 PLEASE SUBMIT MULLION PRODUCT APPROVAL WHICH COMPLIES
 WITH SUBMITTED DESIGN PRESSURE REQUIREMENTS, FBC
 107.21.
  