2022-07-20 11:25:43 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1. CITY OF WEST PALM BEACH IS NOT |
| LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 128. |
| SUBMITTED MIAMI-DADE COUNTY NOA 20-0131.01 SELECTED |
| ROOFING SYSTEMS TYPES A (2) & E (2); GENERAL LIMITATION |
| #7 IS SPECIFICALLY REFERRED TO IN THIS NOA. SUBMIT |
| FASTENER DENSITY CALCULATIONS PREPARED, SIGNED AND |
| SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER, |
| REGISTERED ARCHITECT, OR REGISTERED ROOF CONSULTANT. |
| PROJECT LOCATED IN EXPOSURE D CATEGORY AREA. |
| 2. FBC B 107.2.1. PLEASE CLARIFY: REFERENCE HAS BEEN |
| MADE FOR TWO SEPARATE FLAT/LOW SLOPE ROOF SYSTEMS; |
| MIAMI-DADE COUNTY NOA NO. 20-0131.01 SYSTEM A (2) & E |
| (2); PLEASE CLARIFY SYSTEM TO BE USED. IF USING BOTH |
| SYSTEMS REVISE ROOF SKETCH TO CLEARLY SHOW THE SYSTEM |
| USED ON EACH AREA TO BE REROOFED. |
| 3. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| APPROVALS/NOA'S FOR THE PROPOSED ROOF UNDERLAYMENT TO |
| BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING |
| 4. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020 |
| CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED |
| HIP & RIDGE METAL TO BE USED. (FL5374-R6) |
| 5. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020 |
| CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED |
| HIP & RIDGE TILE ADHESIVE TO BE USED. |
| 6. INSPECTION WAIVERS/ROOFING AFFIDAVITS ARE NOT A PART |
| OF PLAN REVIEW. ALL INSPECTION MATTERS MUST BE ADDRESS |
| BY YOUR BUILDING INSPECTOR. |
| 7. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| DIAGRAM/SKETCH TO INDICATE THE AREAS TO RECEIVE NEW |
| ROOFING CLEARLY IDENTIFIED ON DRAWING. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| |