2022-08-29 10:37:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. APPLICANT SUBMITTED DESIGN PRESSURE CALCULATIONS
 WHICH ARE MUCH LOWER THAN THE DESIGN PRESSURES
 SPECIFIED BY THE ENGINEER. FYI THESE TWO DOCUMENTS HAVE
 BEEN LOCKED SO THEY WILL NOT BE ISSUED.
  
 2. FBC B 1609, SEE SINGLE HUNG NOA, PAGE 2. +65/-80 IS
 HIGHLIGHTED AS THE OPTION PROPOSED. ENGINEER SPECIFIES
 +67/-67. REVISE AND CHECK ALL.
  
  