Plan Review Notes
Plan Review Notes For Permit 22070735
Permit Number 22070735
Review Stop B
Sequence Number 4
Notes
Date Text
2023-04-04 10:44:49PLAN
 REVIEW COMMENTS
  
 4TH REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE PREVIOUS COMMENTS HAVE NOT BEEN ADEQUATELY
 ADDRESSED.
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 5) COMPLIED.
  
 6) PROVISO. TO BE PROVIDED BY THE STAIR MANUFACTURER
 AND APPROVED BY THE DESIGNER OF RECORD BEFORE BEING
 PROVIDED TO THE BUILDING DEPARTMENT AS A SUBMITTAL.
 SUBMIT SHOP DRAWINGS OF THE STAIRS WITH WELD DETAILS.
 FBC 2204.1
  
 7) COMPLIED.
  
 8) NOT RESOLVED. [ SHOW THE HAND RAIL EXTENSIONS AT THE
 TOP PER SECTION 505.10.2 AND AT THE BOTTOM PER SECTION
 505.10.3. SHOW COMPLIANCE WITH FBC ACCESSIBILITY
 SECTION 505 FOR REQUIRED HANDRAILS.
  
 9) COMPLIED.
  
 10) COMPLIED.
  
 11) COMPLIED.
  
 12) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON
 THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED.
  
 13) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 NEW COMMENTS:
  
 14) COMPLIED
  
 15) SHOW COMPLIANCE WITH FBC 1011.11 WHICH REQUIRES
 HANDRAILS ON EACH SIDE OF THE STAIRS.
  
 16) SHOW COMPLIANCE WITH FBC 1014.2 WHICH SPECIFIES THE
 HEIGHT OF THE HANDRAILS TO BE NOT LESS THAN 34" NOR
 MORE THAN 38".
  
 NOTE: IT APPEARS THAT THERE MAY BE A MISUNDERSTANDING
 OF WHAT IS REQUIRED FOR A COMMERCIAL EXIT STAIR. IT
 APPEARS THAT ONE SIDE OF THE STAIR IS AGAINST THE WALL
 OF A BUILDING. A GUARD (RAIL) IS REQUIRED ON THE OPEN
 SIDE OF STAIRS AND LANDINGS AND ARE REQUIRED TO BE NOT
 LESS THAN 42" IN HEIGHT FOR THIS PROJECT. SEE FBC 1015.
 ALSO HANDRAILS ARE REQUIRED ON EACH SIDE OF THE STAIRS.
 FBC1011.11 THE HANDRAIL HEIGHT IS REQUIRED TO BE NOT
 LESS THAN 34" NOR MORE THAN 38" PER FBC 1014.2 AND
 SHALL HAVE EXTENSIONS PER FBC 1014.6 & FBC
 ACCESSIBILITY SECTION 505. FOR COMMERCIAL APPLICATIONS
 THE GUARD (RAILS) ARE NOT ALLOWED TO BE USED AS THE
 HANDRAILS BECAUSE OF THE DIFFERENT HEIGHT REQUIREMENTS.
 IF YOU HAVE ANY QUESTIONS YOU CAN CALL ME AT
 561-805-6714 TO DISCUSS.
  
  