2023-04-04 10:44:49 | PLAN |
| REVIEW COMMENTS |
| |
| 4TH REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| THE PREVIOUS COMMENTS HAVE NOT BEEN ADEQUATELY |
| ADDRESSED. |
| |
| 1) COMPLIED. |
| |
| 2) COMPLIED. |
| |
| 3) COMPLIED. |
| |
| 4) COMPLIED. |
| |
| 5) COMPLIED. |
| |
| 5) COMPLIED. |
| |
| 6) PROVISO. TO BE PROVIDED BY THE STAIR MANUFACTURER |
| AND APPROVED BY THE DESIGNER OF RECORD BEFORE BEING |
| PROVIDED TO THE BUILDING DEPARTMENT AS A SUBMITTAL. |
| SUBMIT SHOP DRAWINGS OF THE STAIRS WITH WELD DETAILS. |
| FBC 2204.1 |
| |
| 7) COMPLIED. |
| |
| 8) NOT RESOLVED. [ SHOW THE HAND RAIL EXTENSIONS AT THE |
| TOP PER SECTION 505.10.2 AND AT THE BOTTOM PER SECTION |
| 505.10.3. SHOW COMPLIANCE WITH FBC ACCESSIBILITY |
| SECTION 505 FOR REQUIRED HANDRAILS. |
| |
| 9) COMPLIED. |
| |
| 10) COMPLIED. |
| |
| 11) COMPLIED. |
| |
| 12) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON |
| THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS |
| MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED. |
| |
| 13) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| |
| NEW COMMENTS: |
| |
| 14) COMPLIED |
| |
| 15) SHOW COMPLIANCE WITH FBC 1011.11 WHICH REQUIRES |
| HANDRAILS ON EACH SIDE OF THE STAIRS. |
| |
| 16) SHOW COMPLIANCE WITH FBC 1014.2 WHICH SPECIFIES THE |
| HEIGHT OF THE HANDRAILS TO BE NOT LESS THAN 34" NOR |
| MORE THAN 38". |
| |
| NOTE: IT APPEARS THAT THERE MAY BE A MISUNDERSTANDING |
| OF WHAT IS REQUIRED FOR A COMMERCIAL EXIT STAIR. IT |
| APPEARS THAT ONE SIDE OF THE STAIR IS AGAINST THE WALL |
| OF A BUILDING. A GUARD (RAIL) IS REQUIRED ON THE OPEN |
| SIDE OF STAIRS AND LANDINGS AND ARE REQUIRED TO BE NOT |
| LESS THAN 42" IN HEIGHT FOR THIS PROJECT. SEE FBC 1015. |
| ALSO HANDRAILS ARE REQUIRED ON EACH SIDE OF THE STAIRS. |
| FBC1011.11 THE HANDRAIL HEIGHT IS REQUIRED TO BE NOT |
| LESS THAN 34" NOR MORE THAN 38" PER FBC 1014.2 AND |
| SHALL HAVE EXTENSIONS PER FBC 1014.6 & FBC |
| ACCESSIBILITY SECTION 505. FOR COMMERCIAL APPLICATIONS |
| THE GUARD (RAILS) ARE NOT ALLOWED TO BE USED AS THE |
| HANDRAILS BECAUSE OF THE DIFFERENT HEIGHT REQUIREMENTS. |
| IF YOU HAVE ANY QUESTIONS YOU CAN CALL ME AT |
| 561-805-6714 TO DISCUSS. |
| |
| |