2023-01-27 11:35:55 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE IS NO INDICATIONS OF A STAIR LADING AT THE |
| EXIT DOOR. |
| |
| PER NFPA 101 CH 7 MEANS OF EGRESS. |
| |
| 7.2.2.3.2 LANDINGS. |
| 7.2.2.3.2.1 STAIRS SHALL HAVE LANDINGS AT DOOR |
| OPENINGS, EXCEPT AS PER MITTED IN 7.2.2.3.2.5 |
| |
| 7.2.2.3.2.3 IN NEW BUILDINGS, EVERY LANDING SHALL HAVE |
| A DIMENSION, |
| MEASURED IN THE DIRECTION OF TRAVEL, THAT IS NOT LESS |
| THAN THE WIDTH OF THE |
| STAIR |
| |
| AS THIS IS NOT A NEW BUILDING BUT A NEW STAIR, NOT AN |
| EXISTING ONE, IT SHALL COMPLY WITH NEW REQUIREMENTS. |
| |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| |
| 2) THERE APPEARS TO BE INDICATIONS OF HANDRAILS ON ONLY |
| ONE SIDE. |
| |
| PER NFPA 101 CH 7 |
| |
| 7.2.2.4.1 HANDRAILS. |
| 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON |
| BOTH SIDES, UNLESS |
| OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR 7.2.2.4.1.6. |
| 7.2.2.4.1.2 IN ADDITION TO THE HANDRAILS REQUIRED AT |
| THE SIDES OF STAIRS BY |
| 7.2.2.4.1.1, BOTH OF THE FOLLOWING PROVISIONS SHALL |
| APPLY: |
| (1) FOR NEW STAIRS, HANDRAILS SHALL BE PROVIDED WITHIN |
| 30 IN. (760 MM) |
| OF ALL PORTIONS OF THE REQUIRED EGRESS WIDTH. |
| (2) FOR EXISTING STAIRS, HANDRAILS SHALL MEET THE |
| FOLLOWING CRITERIA: |
| (A) THEY SHALL BE PROVIDED WITHIN 44 IN. (1120 MM) OF |
| ALL PORTIONS |
| OF THE REQUIRED EGRESS WIDTH. |
| (B) SUCH STAIRS SHALL NOT HAVE THEIR EGRESS CAPACITY |
| ADJUSTED TO A |
| HIGHER OCCUPANT LOAD THAN PERMITTED BY THE CAPACITY |
| FACTOR IN |
| TABLE 7.3.3.1 IF THE STAIR???S CLEAR WIDTH BETWEEN |
| HANDRAILS |
| EXCEEDS 60 IN. (1525 MM) |
| |
| AS THIS IS NOT A NEW BUILDING BUT A NEW STAIR, NOT AN |
| EXISTING ONE, IT SHALL COMPLY WITH NEW REQUIREMENTS. |
| |
| |
| PLEASE REVIEW AND CORRECT OR PROVIDE DETAILED |
| INFORMATION THAT THE OTHER SIDE IS EXISTING OR WILL BE |
| PROVIDED. |
| |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |