Plan Review Notes
Plan Review Notes For Permit 22070735
Permit Number 22070735
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2022-10-20 11:13:20THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PREVIOUS COMMENTS FROM FIRE WERE NOT SPECIFIACCLY
 ADDRESSED BY THE RESUBMITTAL.
  
  
 PREVIOUS COMMENTS ARE RESUBMITTED WITH ADDITIONAL
 COMMENTS IN CAPITAL LETTERS.
  
  
  
 1) THERE IS NO INDICATION OF A SITE PLAN SHOWING THE
 LOCATION OF THE PROPOSED STAIR.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 PLEASE PROVIDE A DETAILED SITE PLAN.
  
 *******THE SITE PLAN DOES NOT PROVIDE THE LOCATION OF
 THE PROPOSED STAIRS.
  
 *******PLEASE PROVIDE THE SPECIFIC LOCATION OF STAIR.
  
  
 2) THERE IS NO INDICATION OF THE EXIT DOOR NOR LANDING
 FROM THE EXIT DOOR.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 PLEASE PROVIDE DETAILS OF THE EXIT DOOR AND EXIT DOOR
 LANDING.
  
  
 *******PLEASE PROVIDE THE TOP OF DECK DIMENSIONS
 LEADING FROM THE UPPER EXIT DOOR.
  
 *******PLEASE PROVIDE THE LOCATION OF THE UPPER EXIT
 DOOR TO ENSURE THERE IS CODE COMPLIANT SPACE FOR THE
 DOOR TO OPEN AND A PERSON CAN STEP OUT TO.
  
  
  
 3) THERE IS NO INDICATION OF THE BOTTOM LANDING AREA
 FROM THE STAIRS THAT IS FREE AND CLEAR TO A PUBLIC WAY.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 PLEASE PROVIDE DETAILS OF THE BOTTOM LANDING AREA.
  
  
 *******PLEASE PROVIDE THE END OF STAIR LANDING
 DIMENSIONS LEADING FROM THE END OF STEPS.
  
 *******PLEASE PROVIDE THAT THERE IS SUFFICIENT SPACE
 FOR A PERSON TO WALK ANY DIRECTION AT THE LANDING; A
 NON-OBSTRUCTED PUBLIC WAY.
  
  
 4) THERE IS NO INDICATION OF ANY WALL NOR
 OPENINGS/WINDOWS ALONG THE EXIT STAIR THAT MAY REQUIRE
 PROTECTION FOR THOSE USING THE EXIT STAIR.
  
 PER NFPA 101 CH 7, MEANS OF EGRESS
  
 7.2.2.5.2.1 WHERE NONRATED WALLS OR UNPROTECTED
 OPENINGS ENCLOSE THE
 EXTERIOR OF A STAIRWAY, OTHER THAN AN EXISTING
 STAIRWAY, AND THE WALLS OR
 OPENINGS ARE EXPOSED BY OTHER PARTS OF THE BUILDING AT
 AN ANGLE OF LESS
 THAN 180 DEGREES, THE BUILDING ENCLOSURE WALLS WITHIN
 10 FT (3050 MM)
 HORIZONTALLY OF THE NONRATED WALL OR UNPROTECTED
 OPENING SHALL BE CON STRUCTED AS REQUIRED FOR STAIRWAY
 ENCLOSURES, INCLUDING OPENING
 PROTECTIVES.
 7.2.2.5.2.2 CONSTRUCTION SHALL EXTEND VERTICALLY FROM
 THE FINISHED GROUND
 LEVEL TO A POINT 10 FT (3050 MM) ABOVE THE TOPMOST
 LANDING OF THE STAIRS
 OR TO THE ROOFLINE, WHICHEVER IS LOWER.
 7.2.2.5.2.3 THE FIRE RESISTANCE RATING OF THE
 SEPARATION EXTENDING 10 FT
 (3050 MM) FROM THE STAIRS SHALL NOT BE REQUIRED TO
 EXCEED 1 HOUR WHERE
 OPENINGS HAVE A MINIMUM 3
 ?4-HOUR FIRE PROTECTION RATING.
  
 PLEASE PROVIDE DETAILS OF ALL OPENINGS ALONG THE WALL.
 IF NOT APPLICABLE, PROVIDE JUSTIFICATION.
  
  
 *******PLEASE PROVIDE AND LOCATE ANY DOORS/WINDOWS
 ALONG THE WALL ABOVE AND BELOW THE STAIRS.
  
 *******ANY OPENINGS PER THE CODE ABOVE ARE REQUIRED TO
 BE PROTECTED/RATED SO THAT FIRE/FLAMES WOULD BE
 PREVENTED VENTING THROUGH THOSE OPENINGS AND BLOCKING
 THIS EXIT STAIR.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  