2022-12-02 13:06:33 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| THE PREVIOUS COMMENTS HAVE NOT BEEN ADEQUATELY |
| ADDRESSED. |
| |
| 1) NOT ADRESSED COMPLETELY. [ CLEARLY INDICATE THE |
| LOCATION OF THE STAIRS ON THE SURVEY.] PROVIDE A |
| PROPERTY SURVEY AND A SITE PLAN THAT SHOWS THE LOCATION |
| OF THE PROPOSED STAIRS. FBC 107.2.1 |
| |
| 2) NOT ADDRESSED. SPECIFY THE OCCUPANCY TYPE AND THE |
| OCCUPANT LOAD THAT THE STAIRS WILL BE SERVICING. FBC |
| 302.1, 1004.1 & 1027.1 |
| |
| 3) NOT ADDRESSED. SPECIFY THE STRUCTURAL DESIGN LOADS |
| FOR THE STAIRS ON THE PLANS. FBC 1603.1 GENERAL. |
| CONSTRUCTION DOCUMENTS SHALL SHOW THE SIZE, SECTION AND |
| RELATIVE LOCATIONS OF STRUCTURAL MEMBERS WITH FLOOR |
| LEVELS, COLUMN CENTERS AND OFFSETS DIMENSIONED. THE |
| DESIGN LOADS AND OTHER INFORMATION PERTINENT TO THE |
| STRUCTURAL DESIGN REQUIRED BY SECTIONS 1603.1.1 THROUGH |
| 1603.1.9 SHALL BE INDICATED ON THE CONSTRUCTION |
| DOCUMENTS. FBC 1603.1.4 WIND DESIGN DATA, FBC 1603.1.1 |
| FLOOR LIVE LOAD (FBC 1607) |
| |
| 4) NOT ADDRESSED. SPECIFY THE FOOTER SIZE AND |
| REINFORCING FOR THE STEEL POSTS THAT ARE SUPPORTING THE |
| STAIRS. FBC 1808.1 |
| |
| 5) NOT ADDRESSED. SPECIFY HOW THE STEEL POSTS WILL BE |
| ATTACHED TO THE FOUNDATION. FBC 1604.8 |
| |
| 5) NOT ADDRESSED. SPECIFY THE LOCATIONS AND AND |
| REQUIRED EMBED DEPTH OF THE 1/2" WEDGE THAT WILL ANCHOR |
| THE LEFT SIDE OF THE STAIRS TO THE WALL OF THE |
| BUILDING. FBC 1603.1 |
| |
| 6) NOT ADDRESSED. SUBMIT SHOP DRAWINGS OF THE STAIRS |
| WITH WELD DETAILS. FBC 2204.1 |
| |
| 7) NOT ADDRESSED. PROVIDE AN ELEVATION OF THE BUILDING |
| THAT SHOWS THE STAIRS ATTACHED. SHOW ALL DOOR AND |
| WINDOW OPENINGS. FBC 107.2.1 & 1027.6 |
| |
| 8) NOT ADDRESSED. SHOW COMPLIANCE WITH FBC |
| ACCESSIBILITY SECTION 505 FOR REQUIRED HANDRAILS. |
| |
| 9) NOT ADDRESSED. SHOW THAT THE STAIR GUARDS COMPLY |
| WITH FBC 1015.3 FOR HEIGHT (42") AND FBC 1015.4 FOR |
| OPENING LIMITATIONS (LESS THAN 4"). |
| |
| 10) NOT ADDRESSED. SPECIFY THE REQUIRED LOADS FOR THE |
| HANDRAILS AND GUARDS. FBC 1607.8 |
| |
| 11) NOT ADDRESSED. [ A FLORIDA LICENSED ARCHITECT OR |
| ENGINEER IS REQUIRED FOR THIS PROJECT.]THE NAME AND THE |
| SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN IS |
| REQUIRED ON THE DRAWINGS. FBC 107.2.1 - INFORMATION ON |
| CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. |
| |
| 12) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON |
| THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS |
| MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED. |
| |
| 13) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| |
| |