2022-08-02 16:01:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE IS NO INDICATION OF A SITE PLAN SHOWING THE |
| LOCATION OF THE PROPOSED STAIR. |
| |
| PER NFPA 1 |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS. |
| |
| 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| |
| PLEASE PROVIDE A DETAILED SITE PLAN. |
| |
| |
| 2) THERE IS NO INDICATION OF THE EXIT DOOR NOR LANDING |
| FROM THE EXIT DOOR. |
| |
| 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| |
| PLEASE PROVIDE DETAILS OF THE EXIT DOOR AND EXIT DOOR |
| LANDING. |
| |
| |
| |
| 3) THERE IS NO INDICATION OF THE BOTTOM LANDING AREA |
| FROM THE STAIRS THAT IS FREE AND CLEAR TO A PUBLIC WAY. |
| |
| 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| |
| PLEASE PROVIDE DETAILS OF THE BOTTOM LANDING AREA. |
| |
| |
| |
| 4) THERE IS NO INDICATION OF ANY WALL NOR |
| OPENINGS/WINDOWS ALONG THE EXIT STAIR THAT MAY REQUIRE |
| PROTECTION FOR THOSE USING THE EXIT STAIR. |
| |
| PER NFPA 101 CH 7, MEANS OF EGRESS |
| |
| 7.2.2.5.2.1 WHERE NONRATED WALLS OR UNPROTECTED |
| OPENINGS ENCLOSE THE |
| EXTERIOR OF A STAIRWAY, OTHER THAN AN EXISTING |
| STAIRWAY, AND THE WALLS OR |
| OPENINGS ARE EXPOSED BY OTHER PARTS OF THE BUILDING AT |
| AN ANGLE OF LESS |
| THAN 180 DEGREES, THE BUILDING ENCLOSURE WALLS WITHIN |
| 10 FT (3050 MM) |
| HORIZONTALLY OF THE NONRATED WALL OR UNPROTECTED |
| OPENING SHALL BE CON STRUCTED AS REQUIRED FOR STAIRWAY |
| ENCLOSURES, INCLUDING OPENING |
| PROTECTIVES. |
| 7.2.2.5.2.2 CONSTRUCTION SHALL EXTEND VERTICALLY FROM |
| THE FINISHED GROUND |
| LEVEL TO A POINT 10 FT (3050 MM) ABOVE THE TOPMOST |
| LANDING OF THE STAIRS |
| OR TO THE ROOFLINE, WHICHEVER IS LOWER. |
| 7.2.2.5.2.3 THE FIRE RESISTANCE RATING OF THE |
| SEPARATION EXTENDING 10 FT |
| (3050 MM) FROM THE STAIRS SHALL NOT BE REQUIRED TO |
| EXCEED 1 HOUR WHERE |
| OPENINGS HAVE A MINIMUM 3 |
| ?4-HOUR FIRE PROTECTION RATING. |
| |
| PLEASE PROVIDE DETAILS OF ALL OPENINGS ALONG THE WALL. |
| IF NOT APPLICABLE, PROVIDE JUSTIFICATION. |
| |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |