Plan Review Notes For Permit 22070679 |
Permit Number |
22070679 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-09-07 17:26:13 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) NOT RESOLVED. THE DIGITAL SIGNATURE ON THE | | STRUCTURAL ANALYSIS COULD NOT BE VERIFIED. SEE | | SIGNATURE REVIEW STOP. | | | | 2) NOT RESOLVED. THE ENERGY CALCULATION FORM IS NOT | | SIGNED. THE PREPARER AND THE OWNER/AGENT IS REQUIRED TO | | SIGN AND DATE THE ENERGY FORM (R405-2020). FBC ENERGY | | CONSERVATION R405.2.1 | | | | 3) RESOLVED. | | | | 4) RESOLVED. PRODUCT APPROVALS FOR ROOFING MATERIALS | | HAVE BEEN DEFERRED. | | | | 5) NO LETTER FOR ASBESTOS COMPLIANCE WAS SUBMITTED. SEE | | ASBESTOS REVIEW STOP. | | | | 6) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | |
|