| 22070634 4065 N HAVERHILL RD # B1 |
| |
| 2ND REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| NEW COMMENT; GENERAL: THE SUBMITTED PLUMBING PLAN |
| (SINGLE PAGE) IS MIXING EXISTING WITH NEW AND IS VERY |
| UNCLEAR REGARDING THE MATTER; ADDITIONALLY, IT IS |
| CRAMMING ALL THE INFORMATION FOR GAS AND PLUMBING ONTO |
| A SINGLE PAGE. PER WPB FBC 107.2.1, TO PROVIDE CLARITY, |
| PLEASE PROVIDE A SEPARATE EXISTING/DEMO PLAN, A |
| SEPARATE PROPOSED PLAN. BR PREPARED TO ADD PAGES AS |
| APPLICABLE TO PROVIDE ADEQUATE INFORMATION. |
| |
| 1. SIGNATURES APPROVED |
| |
| 2.THE BACKFLOW PERMIT AND INTERCEPTOR PERMITS ARE |
| REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE |
| PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN |
| APPLICATION 'TBD' (TO BE DETERMINED) IF YOU DO NOT HAVE |
| A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| APPLICATION TO [email protected] . YOU WILL |
| RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. |
| |
| 3. PARTIALLY COMPLIED: GREASE INTERCEPTOR: A SEPARATE |
| PERMIT IS REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER |
| THE MAIN PERMIT IS ALSO REQUIRED. |
| ***E) ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY THE |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC |
| 107.2.1, 107.3.4. |
| NEW COMMENT: CALCULATIONS FOR GREASE INTERCEPTOR SHALL |
| NOT INCLUDE HAND SINKS. FBC PL 1003.2. IF MOP SINK AND |
| PREP SINK DISCHARGE TO GREASY WASTE THEN THEY SHALL BE |
| INCLUDED IN CALCULATIONS. |
| NEW COMMENT: GREASE TRAP SUBMITTAL DOES NOT INDICATE |
| THE SIZE OF THE INTERCEPTOR TO BE USED. PLEASE INDICATE |
| THE MODEL NUMBER/SIZE ON THE SUBMITTAL. THE |
| INLET/OUTLET PORTS SHALL BE SIZED TO ACCOMMODATE IN |
| SIZE OF THE INLET AND OUTLET SIZE OF THE PIPING. FBC PL |
| 704.2 |
| NEW COMMENT: RISER DIAGRAM SHOWS A 2-WAY CLEANOUT |
| UPSTREAM AND DOWNSTREAM OF THE INTERCEPTOR BUT THEY |
| APPEAR TO BE A CROSS TEE IN THE DIAGRAM. PLEASE SHOW A |
| 2WAY CO TEE WITH A SMOOTH HORIZONTAL BOTTOM. A |
| DEPRESSED/TRAPPED BOTTOM IS NOT ALLOWED |
| |
| 7.SECOND REQUEST: PLAN SHEET S-3: PER FBC ACC 609.4, |
| GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE THE |
| FINISH FLOOR MEASURED TO THE TOP (NOT THE CENTER) OF |
| THE GRIPPING SURFACE |
| REVISED DETAIL ON S-3 SHOWS 32 INCHES MAXIMUM TO |
| CENTER; NOTES ON S-1 CORRECT THE SITUATION. PLEASE |
| CORRECT OR ELIMINATE INCORRECT DIMENSIONS ON DETAIL. |
| |
| 9. & 10. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE |
| PLUMBING FLOOR PLAN SHOWING SANITARY AND WATER |
| DISTRIBUTION. RECONCILE CONFIGURATION WITH THE RISER |
| DIAGRAMS (I.E., ADDED BATHROOM IS BACK TO BACK ON FLOOR |
| PLAN, RISER DIAGRAM SHOWS SIDE BY SIDE). ALL |
| ITEMS/COMPONENTS, INCLUDING BUT NOT LIMITED TO WATER |
| HEATER, RECIRCULATING PUMP, ETC., EXISTING AND NEW |
| SHALL BE INCLUDED ON PLAN VIEW AND RISER DIAGRAMS. |
| EXISTING SHALL BE NOTED AS SUCH. INCLUDE SERVICE ENTRY |
| TO UNIT. SIZE ALL PIPING SEGMENTS. |
| TO BE CLEAR, PLAN VIEW AND RISER DIAGRAM SHOULD REFLECT |
| EACH OTHER |
| ALL FIXTURES AND EQUIPMENT SHOWN ON THE PLANS REQUIRING |
| CONNECTIONS SHALL BE SHOWN CONNECTED TO THE PIPING |
| SYSTEMS |
| NEW COMMENT: PROVIDE VTR FOR GREASY WASTE SYSTEM. FBC |
| PL 904.1, 904.1.1, 904.1.2 |
| |
| 11. SECOND REQUEST: PER FBC PL 608.1, SPECIFY AND |
| PROVIDE BACKFLOW PREVENTER FOR ICE MACHINES. |
| TO BE CLEAR; A BFP IS REQUIRED FOR EACH ICE MACHINE. |
| INDICATE THE SAME ON THE PLANS |
| |
| 13. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE |
| INSULATION SPECIFICATION SPEC FOR HOT WATER INSULATION |
| COMPLY WITH FBC EC C404.4 (A-E) AND TABLE C403.2.10. |
| THE FOLLOWING PIPING SHALL BE INSULATED TO LEVELS SHOWN |
| IN TABLE C403.2.10: |
| ***A) RECIRCULATING SYSTEM PIPING, INCLUDING THE SUPPLY |
| AND RETURN PIPING OF A CIRCULATING TANK TYPE WATER |
| HEATER. |
| |
| |
| 16.PARTIALLY COMPLIED: EXISTING WATER HEATER: PER WPB |
| FBC 107.2.1, PROVIDE THE FOLLOWING; |
| ***B) PROVIDE TEMPERATURE OF HOT WATER TO DISTRIBUTION |
| ***E) WATER HEATER/RECIRC PUMP DETAIL SCHEDULE & |
| DETAIL- PROVIDE DETAIL INTEGRATING WATER HEATER AND |
| RECIRC PUMP; SHOW ALL VALVES AND APPURTENANCES. |
| ***G) PLEASE CLARIFY MIXING VALVE AT WATER HEATER ON |
| HOT WATER OUTLET. |
| TO BE CLEAR, PROVIDE DETAIL FOR MIXING VALVE AND |
| CONFORM TO ASSE 1017. FBC PL 607.1.1, 613.1 |
| |
| 21. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE DETAIL |
| FOR STEAM TABLE AND INDIRECT WASTE SHOWING COMPLIANCE |
| WITH FBC PL 802.1.1. |
| |
| 22. PER 802.1, FLOOR DRAINS LOCATED WITHIN WALK-IN |
| REFRIGERATORS OR FREEZERS IN FOOD SERVICE AND FOOD |
| ESTABLISHMENTS SHALL BE INDIRECTLY CONNECTED TO THE |
| SANITARY DRAINAGE SYSTEM BY MEANS OF AN AIR GAP. |
| TO BE CLEAR, PROVIDE DETAIL |
| NEW COMMENT: DOES THIS DRAIN CONTRIBUTE FAT, OIL OR |
| GREASE (FOG) TO THE SYSTEM. IF SO, DISCHARGE THE |
| RECEPTOR TO THE GREASY WASTE AND ADD TO THE |
| CALCULATIONS FOR THE INTERCEPTOR. IF NOT, DISCHARGE TO |
| SANITARY |
| |
| 23. HOT WATER DISTRIBUTION IS CORRECTLY NOTED TO BE |
| RECIRCULATING, BUT THERE IS NO LOOP. PER WPB FBC |
| 107.2.1, CLARIFY. |
| TO BE CLEAR, SHOW COMPLETED LOOP |
| NEW COMMENT: HOT WATER IS REQUIRED AT THE #7 MOP SINK |
| AS WELL AS THE #8 PREP SINK WHICH IS NOT SHOWN IN THE |
| WATER DISTRIBUTION RISER DIAGRAM. FBC PL 607.1 |
| |
| 31. SECOND REQUEST: ICE MAKER(S), HAND SINKS, STEAM |
| TABLE AND SERVICE SINKS SHALL NOT DISCHARGE TO THE |
| GREASY WASTE PER FBC PL 1003.2. |
| TO BE CLEAR, #11 STEAM TABLE, #2 ICE MAKER DRAIN, #4 |
| ICE MAKER DRAIN SHALL NOT DISCHARGE TO GREASE |
| INTERCEPTOR. FBC PL 1003.2. IT IS DETERMINED THE #7 MOP |
| SINK (SERVICE SINK) MAY DISCHARGE TO THE GREASE |
| INTERCEPTOR. |
| NEW COMMENT: PROVIDE WASTE, HOT AND COLD WATER FOR #8 |
| PREP SINK PER FBC PL 301.3, 602.2, 607.1; IS IT A FOOD |
| PREP SINK? IF SO, COMPLY WITH FBC PL 802.1.1 OR 801.1.7 |
| AS APPLICABLE. IF THE WASTE CONTRIBUTES FAT, OIL OR |
| GREASE (FOG) WASTE RECEPTOR SHALL CONNECT TO GREASY |
| WASTE. IF NOT, CONNECT RECEPTOR TO SANITARY. |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |