Plan Review Notes
Plan Review Notes For Permit 22070634
Permit Number 22070634
Review Stop M
Sequence Number 2
Notes
Date Text
2022-11-29 16:33:412ND REVIEW FMC
 PERMIT: 22070634
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REVISE THE MECHANICAL DRAWING TO INDICATE THAT THE
 RETURNS IN THE KITCHEN WILL COMPLY WITH FMC 601.5
 BELOW:
 601.5 RETURN AIR OPENINGS. RETURN AIR OPENINGS FOR
 HEATING, VENTILATION AND AIR-CONDITIONING SYSTEMS SHALL
 COMPLY WITH ALL OF THE FOLLOWING:
 1. OPENINGS SHALL NOT BE LOCATED LESS THAN 10 FEET
 (3048 MM) MEASURED IN ANY DIRECTION FROM AN OPEN
 COMBUSTION
 CHAMBER OR DRAFT HOOD OF ANOTHER APPLIANCE LOCATED IN
 THE SAME ROOM OR SPACE.
  
 2) SECOND REQUEST: PROVIDE THE OUTDOOR AIR CALCULATIONS
 FOR THIS TENANT SPACE BASED ON EACH USE OF SPACE. THE
 OCCUPANCY CLASSIFICATION COLUMN OF TABLE 403.3.1.1
 SHALL BE USE. FMC 403.3.1.1
  
 3) SIDE NOTE: REMOVE THE MODEL ELES BLACK OVERLAYS FROM
 THE HOOD DRAWINGS BEFORE YOU SUBMIT THE DRAWINGS FOR
 THE SEPARATE HOOD PERMIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  