2022-12-06 13:58:15 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 22070634 4065 N HAVERHILL RD # B1 |
| |
| 2ND REVIEW |
| |
| GAS COMMENTS: DENIED |
| |
| |
| NEW COMMENT #1: GENERAL: THE SUBMITTED PLUMBING PLAN |
| (SINGLE PAGE) IS MIXING EXISTING WITH NEW AND IS VERY |
| UNCLEAR REGARDING THE MATTER; ADDITIONALLY, IT IS |
| CRAMMING ALL THE INFORMATION FOR GAS AND PLUMBING ONTO |
| A SINGLE PAGE. PER WPB FBC 107.2.1, TO PROVIDE CLARITY, |
| PLEASE PROVIDE A SEPARATE EXISTING/DEMO PLAN, A |
| SEPARATE PROPOSED PLAN AS APPLICABLE. BE PREPARED TO |
| ADD PAGES AS APPLICABLE TO PROVIDE ADEQUATE |
| INFORMATION. |
| |
| |
| NEW COMMENT #2: SHOW COMPLIANCE FOR ELECTRICAL BONDING |
| PER 2020 FGC 310 |
| |
| |
| 1. SIGNATURES APPROVED |
| |
| |
| |
| 4. SECOND REQUEST: PER WPB FBC 107.2.1, PLEASE INDICATE |
| THE TYPE OF GAS (LP OR NATURAL) |
| TO BE CLEAR, PLEASE NOTE NATURAL OR LP ON THE PLAN |
| |
| |
| |
| 5 SECOND REQUEST: PER WPB FBC 107.2.1, WPB FBC |
| 107.3.5.1.5, FBC FG 301.1, INCLUDE ON THE RISER DIAGRAM |
| THE FOLLOWING: |
| ***A.THE LOCATION OF SHUTOFFS AND REGULATORS. |
| ***B.SUPPLY PRESSURE AND SYSTEM PRESSURES BETWEEN |
| REGULATORS |
| TO BE CLEAR, PLEASE INCLUDE SYSTEM PRESSURE BETWEEN |
| METER/REGULATOR AND 9.5-13 INCH WC REGULATOR |
| ***C.INCLUDE ALL PIPE LENGTHS (SEGMENTS), BTU LOADS, |
| AND DISTANCES TO THE APPLIANCES THAT WERE USED TO |
| CALCULATE MINIMUM PIPE SIZES USING THE SIZING TABLES |
| FROM THE 2020 FBC FG 402 (INCLUDE REFERENCES TO THE |
| TABLE(S) USED) |
| |
| TO BE CLEAR, |
| |
| * PROVIDE LENGTHS OF ALL PIPE SEGMENTS (VERTICAL AND |
| HORIZONTAL) FROM 9.5-13 INCH WC REGULATOR TO ALL |
| APPLIANCES AND OUTLETS AND FROM METER/REGULATOR TO |
| 9.5-13 INCH WC REGULATOR; SHOW FULL RUNOUTS TO |
| APPLIANCES. |
| |
| *PROVIDE SIZES OF ALL SEGMENTS |
| |
| *CLARIFY PRESSURE OF EACH SYSTEM FROM 9.5-13 INCH WC |
| REGULATOR TO ALL APPLIANCES AND OUTLETS AND FROM |
| METER/REGULATOR TO 9.5-13 INCH WC REGULATOR |
| |
| *PROVIDE TABLES (FBC FG 402) USED IN SIZING OF THE TWO |
| SYSTEMS |
| |
| |
| |
| |
| 6. SECOND REQUEST: PER WPB FBC 107.2.1, LABEL ON THE |
| RISER DIAGRAM ALL TYPES OF GAS PIPING MATERIALS BEING |
| INSTALLED. FBC FG 403.1 |
| |
| |
| |
| 8. SECOND REQUEST: PER WPB FBC 107.2.1, INCLUDE |
| CALCULATIONS FOR COMBUSTION AIR PER 2020 FBC FG 304.1 |
| |
| |
| |
| 9. SECOND REQUEST: PER WPB FBC 107.2.1, WPB FBC |
| 107.3.5.1.5, FBC FG 301.1, PROVIDE A PLAN SHOWING THE |
| PIPING DISTRIBUTION, UTILITIES METER/REGULATOR, |
| EMERGENCY SHUT OFF VALVE, MP REGULATORS, LISTED |
| SHUT-OFF VALVES, EACH APPLIANCE, ITS LOCATION AND |
| CORRESPONDING BTU LOAD ON THE PLAN. RECONCILE PLAN VIEW |
| AND RISER DIAGRAM |
| |
| TO BE CLEAR, A PLAN VIEW IS REQUIRED WHICH SHOWS |
| *DISTRIBUTION OF GAS PIPE |
| *LOCATION AND ID OF EACH APPLIANCE WITH BTU LOAD, |
| *LOCATION OF METER/ REGULATOR |
| *9.5-13 INCH WC REGULATOR |
| *SHUT OFF VALVES |
| *EMERGENCY SHUT OFF VALVE |
| |
| |
| |
| |
| 10. PARTIALLY COMPLIED: PER WPB FBC 107.2.1, PROVIDE |
| THE DELIVERY PRESSURE FROM THE UTILITIES |
| METER/REGULATOR |
| PLEASE NOTE THAT IF MP REGULATORS ARE REQUIRED (AS |
| SEEMS TO BE THE CASE) THE DOWNSTREAM SIDE OF THE MP |
| REGULATOR IS A SECOND SYSTEM AND SHALL BE CALCULATED |
| SEPARATELY. |
| |
| TO BE CLEAR, PROVIDE DELIVERY PRESSURE FROM UTILITIES |
| METER/REGULATOR TO 9.5-13 INCH WC REGULATOR IN ADDITION |
| TO PROVIDED DELIVERY PRESSURE FROM 9.5-13 INCH WC |
| REGULATOR TO APPLIANCES |
| |
| |
| |
| 11. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE |
| DISTANCE FROM EACH REG TO FURTHEST POINT (PER SYSTEM) |
| |
| TO BE CLEAR, PROVIDE DISTANCE FROM UTILITIES |
| METER/REGULATOR TO 9.5-13 INCH WC REGULATOR AND THEN |
| FROM 9.5-13 INCH WC REGULATOR TO FURTHEST APPLIANCE |
| CONNECTION |
| |
| |
| |
| |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |