Plan Review Notes
Plan Review Notes For Permit 22070634
Permit Number 22070634
Review Stop P
Sequence Number 1
Notes
Date Text
2022-07-26 15:12:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22070634 4065 N HAVERHILL RD # B1
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.THERE ARE NO ELECTRONIC SIGNATURES FOR PLUMBING AND
 GAS. ENGINEER'S STAMP ON PDF DOES NOT HAVE A SIGNATURE
 AND DATE. SEE SIGNATURES.
  
 2.THE BACKFLOW PERMIT AND INTERCEPTOR PERMITS ARE
 REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE
 PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN
 APPLICATION 'TBD' (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
  
 3. GREASE INTERCEPTOR: A SEPARATE PERMIT IS REQUIRED
 HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN PERMIT IS
 ALSO REQUIRED.
 ***A) PROVIDE AN ENLARGED PIPING DIAGRAM SHOWING THE
 LOCATIONS OF CLEANOUTS AND VENTS AS REQUIRED BY THE
 MANUFACTURER AND FBC PL 1003.9.
 ***B) PROVIDE AN EQUIPMENT SCHEDULE FOR THE INTERCEPTOR
 ON THE PLAN AND SUBMIT MANUFACTURER'S SPECIFICATIONS
 THAT INDICATE THE LISTING AND LABELING OF THE UNIT- FBC
 PL 1003.3.5.
 ***C) PROVIDE A SITE SPECIFIC, DIMENSIONED INSTALLATION
 DIAGRAM SHOWING THE BURIAL DEPTH AND INLET AND OUTLET
 LOCATIONS, CLEAN OUT AND SAMPLING PORT LOCATIONS AND
 SIZES. PLEASE NOTE A SAMPLING PORT CONSISTING OF A
 4-INCH TWO-WAY CLEANOUT TO BE USED AS A SAMPLING PORT
 MAY BE REQUIRED. PLEASE CONTACT THE CITY OF WEST PALM
 BEACH UTILITIES DEPT. FOR ADDITIONAL REQUIRED
 INSPECTION AND TEST SAMPLING INFORMATION AND
 GUIDELINES: FOG COMPLIANCE SPECIALISTS AT 561-822-2065
 OR 561-822-2274 OR EMAIL [email protected].
 ***D) PER FBC PL 305.7 & 1003.10, PLEASE SUBMIT SPECS
 FOR THE ACCESS AND LIDS.
 ***E) ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY THE
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC
 107.2.1, 107.3.4.
  
 4.PLAN SHEET S-3: ALL REFERENCES TO FLORIDA
 ACCESSIBILITY CODE SHALL BE NOTED 2020, NOT 2017 PER
 WPB FBC 107.2.1.
  
 5.PLAN SHEET S-3/TYPICAL ACCESSIBLE RESTROOM NOTE 4:
 PER FBC ACC 603.3, DIMENSION SHALL BE TO THE BOTTOM OF
 THE REFECTING SURFACE. PER WPB FBC 107.2.1, CLARIFY THE
 NOTE.
  
 6.PLAN SHEET S-3: THE SEAT HEIGHT OF A WATER CLOSET
 ABOVE THE FINISH FLOOR SHALL BE 17 INCHES (430 MM)
 MINIMUM AND 19 INCHES (485 MM) MAXIMUM MEASURED TO THE
 TOP OF THE SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO
 A LIFTED POSITION PER FBC ACC 604.4.
  
 7.PLAN SHEET S-3: PER FBC ACC 609.4, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP (NOT THE CENTER) OF THE GRIPPING SURFACE
  
 8.PLAN SHEET S-1/WALL FINISHES: PER FBC 1210.2.2, FBC
 PL 310.3, WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NON-ABSORBENT SURFACE PER FBC 1210.2.2. SECTION
 1210.2.2 STIPULATES THAT THE MATERIAL BE "HARD." THE
 INTENT OF THIS SECTION IS THAT THE SURROUNDING MATERIAL
 SHOULD NOT BE OF A TYPE THAT IS EASILY DAMAGED SUCH
 THAT THE MATERIAL COULD BECOME ABSORBENT AND THUS, NOT
 READILY CLEANABLE AND SANITIZED. PAINTED DRYWALL, EVEN
 WHERE COATED WITH HIGHLY DURABLE PAINTS, DOES NOT MEET
 THE INTENT OF SECTION 1210.2.2. THE TYPICAL MATERIALS
 USED FOR THIS APPLICATION ARE CERAMIC TILE, FIBERGLASS
 REINFORCED PLASTIC (FRP) PANELS, PHENOLIC PANELS,
 LAMINATED PLASTIC PANELS, PAINTED STEEL AND STAINLESS
 STEEL.
  
 9. PER WPB FBC 107.2.1, PROVIDE PLUMBING FLOOR PLAN
 SHOWING WATER DISTRIBUTION. RECONCILE CONFIGURATION
 WITH THE RISER DIAGRAMS (I.E., ADDED BATHROOM IS BACK
 TO BACK ON FLOOR PLAN, RISER DIAGRAM SHOWS SIDE BY
 SIDE). ALL ITEMS/COMPONENTS, INCLUDING BUT NOT LIMITED
 TO WATER HEATER, RECIRCULATING PUMP, ETC., EXISTING AND
 NEW SHALL BE INCLUDED ON PLAN VIEW AND RISER DIAGRAMS.
 EXISTING SHALL BE NOTED AS SUCH. INCLUDE SERVICE ENTRY
 TO UNIT. SIZE ALL PIPING SEGMENTS.
  
 10. PER WPB FBC 107.2.1, PLUMBING FLOOR PLAN SHOWING
 SANITARY PIPING SHALL BE RECONCILED CONFIGURATIONS WITH
 THE RISER DIAGRAM (I.E., ADDED BATHROOM IS BACK TO BACK
 ON FLOOR PLAN, RISER DIAGRAM SHOWS SIDE BY SIDE). ALL
 ITEMS/COMPONENTS, INCLUDING BUT NOT LIMITED TO, GREASE
 INTERCEPTOR, FLOOR DRAINS, FLOOR SINKS, ETC., EXISTING
 AND NEW SHALL BE INCLUDED ON PLAN VIEW AND RISER
 DIAGRAMS. EXISTING SHALL BE NOTED AS SUCH. SIZE ALL
 PIPING SEGMENTS.
  
 11. PER FBC PL 608.1, SPECIFY AND PROVIDE BACKFLOW
 PREVENTER FOR ICE MACHINES.
  
 12. PER WPB FBC 107.2.1, PROVIDE PIPING MATERIAL SPEC
 FOR WATER, SANITARY TO INCLUDE PIPE, VALVES, FITTINGS
 AND JOINTS. COMPLY WITH FBC PL CHAPTERS 6, 7, AND 9
  
 13. PER WPB FBC 107.2.1, PROVIDE INSULATION
 SPECIFICATION SPEC FOR HOT WATER INSULATION COMPLY WITH
 FBC EC C404.4 (A-E) AND TABLE C403.2.10.
 THE FOLLOWING PIPING SHALL BE INSULATED TO LEVELS SHOWN
 IN TABLE C403.2.10:
 ***A) RECIRCULATING SYSTEM PIPING, INCLUDING THE SUPPLY
 AND RETURN PIPING OF A CIRCULATING TANK TYPE WATER
 HEATER.
 ***B) THE FIRST 8 FEET OF OUTLET PIPING FOR A
 CONSTANT-TEMPERATURE NONRECIRCULATING STORAGE SYSTEM.
 ***C) THE FIRST 8 FEET OF BRANCH PIPING CONNECTING TO
 RECIRCULATED, HEAT-TRACED, OR IMPEDANCE HEATED PIPING.
 ***D) THE INLET PIPING BETWEEN THE STORAGE TANK AND A
 HEAT TRAP IN A NONRECIRCULATING STORAGE SYSTEM.
 ***E) PIPING THAT IS EXTERNALLY HEATED (SUCH AS HEAT
 TRACE OR IMPEDANCE HEATING).
  
 14. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL
 BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND
 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS
 STATING THE SAME.
  
 15. PER WPB FBC 107.2.1, PROVIDE NOTE ON PIPE HANGER
 DETAIL STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 16.EXISTING WATER HEATER: PER WPB FBC 107.2.1, PROVIDE
 THE FOLLOWING;
 ***A) PROVIDE ENERGY EFFICIENCY FOR WATER HEATER;
 COMPLY WITH FBC EC TABLE C404.2
 ***B) PROVIDE TEMPERATURE OF HOT WATER TO DISTRIBUTION
 ***C) PER WPB FBC 107.2.1, PROVIDE THE MANUFACTURER,
 MODEL, SIZE, SPECIFICATION AND INSTALLATION MANUAL FOR
 EXISTING WATER HEATER. BE SURE TO INDICATE STORAGE TYPE
 OR TANKLESS, GAS OR ELECTRIC.
 ***E) WATER HEATER/RECIRC PUMP DETAIL SCHEDULE &
 DETAIL- PROVIDE DETAIL INTEGRATING WATER HEATER AND
 RECIRC PUMP; SHOW ALL VALVES AND APPURTENANCES.
 ***F) PROVIDE SCHEDULE AND SPEC FOR THE RECIRC PUMP
 ***G) PLEASE CLARIFY MIXING VALVE AT WATER HEATER ON
 HOT WATER OUTLET
  
 17.PER WPB FBC 107.2.1, PROVIDE DETAIL FOR TMV (ASSE
 1070) AT LAVATORIES AND SINKS.
  
 18. WATER HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010.
  
 19.PER WPB FBC 107.2.1, SHOW WATER HAMMER ARRESTORS IN
 WATER RISER.
  
 20. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THREE
 COMPARTMENT SINK AND INDIRECT WASTE SHOWING COMPLIANCE
 WITH FBC PL 802.1.
  
 21. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR STEAM TABLE
 AND INDIRECT WASTE SHOWING COMPLIANCE WITH FBC PL
 802.1.1.
  
 22. PER 802.1, FLOOR DRAINS LOCATED WITHIN WALK-IN
 REFRIGERATORS OR FREEZERS IN FOOD SERVICE AND FOOD
 ESTABLISHMENTS SHALL BE INDIRECTLY CONNECTED TO THE
 SANITARY DRAINAGE SYSTEM BY MEANS OF AN AIR GAP.
  
 23. HOT WATER DISTRIBUTION IS CORRECTLY NOTED TO BE
 RECIRCULATING, BUT THERE IS NO LOOP. PER WPB FBC
 107.2.1, CLARIFY.
  
 24. P-1/SANITARY SLAB DETAIL: THE DETAIL SHOWS PIPE
 WITHIN THE SLAB. THE PIPING SHOULD BE IN THE SOIL
 BENEATH THE SLAB. PER WPB FBC 107.2.1, CLARIFY; PROVIDE
 A CORRECTED SLAB REPAIR DETAIL. SHOW THE WIDTH OF THE
 REPAIR, THE MINIMUM THICKNESS AND PSI OF THE CONCRETE
 TO BE REPLACED. SHOW SIZE, LENGTH, SPACING (ON CENTER),
 MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE MATERIAL FOR
 DOWELS. THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT
 OF THE SOIL AS WELL AS THE REQUIRED VAPOR BARRIER OVER
 WELL COMPACTED SOIL. A COPY OF THE TERMITE CERTIFICATE
 SHALL BE ONSITE FOR FINAL INSPECTION.
  
 25.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL
 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE PIPING
 LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF
 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE
 A MINIMUM SLOPE OF 1/8 INCH PER FOOT."
  
 26. PER WPB FBC 107.2.1, PROVIDE FIXTURE SCHEDULE AND
 SPEC
  
 27. PER WPB FBC 107.2.1, PROVIDE DRAIN SCHEDULE AND
 SPEC
  
 28. PER WPB FBC 107.2.1, PROVIDE FIXTURE SCHEDULE WITH
 DFU AND DRAIN SIZE/WATER SUPPLY FU AND CONNECTION SIZE
  
 29. PER WPB FBC 107.2.1, PROVIDE WATER SIZING
 CALCULATIONS
  
 30. PER WPB FBC 107.2.1, PROVIDE SANITARY SIZING
 CALCULATIONS
  
 31. ICE MAKER(S), HAND SINKS, STEAM TABLE AND SERVICE
 SINKS SHALL NOT DISCHARGE TO THE GREASY WASTE PER FBC
 PL 1003.2.
  
 32. MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL
 FOR THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING:
 ***A) WATER HEATER
 ***B) RECIRCULATING PUMP
 ***C) BACKFLOW PREVENTER DEVICES
 ***D) THERMOSTATIC MIXING VALVES
 ***E)KITCHEN EQUIPMENT
  
 33. PER WPB FBC 107.2.1, PROVIDE A NOTE REQUIRING A
 SIGN TO BE DISPLAYED STATING "DRINKING WATER IS
 PROVIDED FREE OF CHARGE IN A FLAT BOTTOM GLASS/CUP"
  
 34.PER WPB FBC 107.2.1, PLEASE HIDE ALL STICKY NOTES ON
 PDFS AS THEY INTERFERE WITH INTERPRETING THE PLANS.
  
 END OF COMMENTS.
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  