2022-07-26 16:44:17 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE |
| PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 22070634 4065 N HAVERHILL RD # B1 |
| |
| 1ST REVIEW |
| GAS COMMENTS: DENIED |
| |
| 1. THERE ARE NO ELECTRONIC SIGNATURES FOR PLUMBING AND |
| GAS. ENGINEER'S STAMP ON PDF DOES NOT HAVE A SIGNATURE |
| AND DATE. SEE SIGNATURES. |
| |
| 2. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S |
| SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA 58, AND FBC FG 402.2, AND 301.3. THE INSTALLATION |
| MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE |
| ONSITE AT THE TIME OF INSPECTION. FBC FG 305.1. |
| |
| 3.PER WPB FBC 107.2.1, PLEASE HIDE ALL STICKY NOTES ON |
| PDFS AS THEY INTERFERE WITH INTERPRETING THE PLANS. |
| |
| 4. PER WPB FBC 107.2.1, PLEASE INDICATE THE TYPE OF GAS |
| (LP OR NATURAL) |
| |
| 5 PER WPB FBC 107.2.1, INCLUDE ON THE RISER DIAGRAM THE |
| FOLLOWING: |
| A. THE LOCATION OF SHUTOFFS AND REGULATORS. |
| B. SUPPLY PRESSURE AND SYSTEM PRESSURES BETWEEN |
| REGULATORS |
| C. INCLUDE ALL PIPE LENGTHS (SEGMENTS), BTU LOADS, AND |
| DISTANCES TO THE APPLIANCES THAT WERE USED TO CALCULATE |
| MINIMUM PIPE SIZES USING THE SIZING TABLES FROM THE |
| 2020 FGC 402 (INCLUDE REFERENCES TO THE TABLE(S) USED) |
| |
| 6. PER WPB FBC 107.2.1, LABEL ON THE RISER DIAGRAM ALL |
| TYPES OF GAS PIPING MATERIALS BEING INSTALLED 2020 FGC |
| 403 |
| |
| 7. PER WPB FBC 107.2.1, PROVIDE SIZE AND MATERIAL FOR |
| UNDERGROUND SLEEVE; PROVIDE DETAIL(S) FOR |
| TERMINATIONSINTERIOR AND EXTERIOR |
| |
| 8.I PER WPB FBC 107.2.1, INCLUDE CALCULATIONS FOR |
| COMBUSTION AIR PER 2020 FGC 304 |
| |
| 9. PER WPB FBC 107.2.1, PROVIDE A PLAN SHOWING THE |
| PIPING DISTRIBUTION, UTILITIES METER/REGULATOR, |
| EMERGENCY SHUT OFF VALVE, MP REGULATORS, LISTED |
| SHUT-OFF VALVES, EACH APPLIANCE, ITS LOCATION AND |
| CORRESPONDING BTU LOAD ON THE PLAN. RECONCILE PLAN VIEW |
| AND RISER DIAGRAM |
| |
| 10. PER WPB FBC 107.2.1, PROVIDE THE DELIVERY PRESSURE |
| FROM THE UTILITIES METER/REGULATOR |
| PLEASE NOTE THAT IF MP REGULATORS ARE REQUIRED (AS |
| SEEMS TO BE THE CASE) THE DOWNSTREAM SIDE OF THE MP |
| REGULATOR IS A SECOND SYSTEM AND SHALL BE CALCULATED |
| SEPARATLY. |
| |
| 11. PER WPB FBC 107.2.1, PROVIDE DISTANCE FROM REG TO |
| FURTHEST POINT (PER SYSTEM) |
| |
| 12. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR EMERGENCY |
| HOOD SHUT DOWN VALVE. THE VALVE SHALL BE BELOW THE |
| CEILING. UNION TO BE DOWN STREAM OF MANUAL VALVE. SECS. |
| 10.4, 10.5 OF NFPA 96-17. |
| |
| 13. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE |
| INSTALLATION OF THE MP REGULATOR(S) SHOWING COMPLIANCE |
| WITH FBC FG 409.4, 410.2(5)(6)(7). |
| |
| 14.PER WPB FBC 107.2.1, SUBMIT MANUFACTURERS |
| SPECIFICATIONS FOR REGULATORS. |
| |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER PX928 |
| PLUMBING INSPECTOR BN2148 |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-246-0882 |
| PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| THURSDAYS |
| |