2022-07-21 12:59:44 | FIRE REVIEW COMMENTS: |
| |
| (1) SHEET S-1 INDICATES A BUSINESS OCCUPANCY WITH 41 |
| TOTAL OCCUPANCY. PER NFPA 101 THIS WOULD BE DEFINED AS |
| A MERCANTILE OCCUPANCY. SHEET LS-1 INDICATES AN |
| OCCUPANT LOAD OF 78, WHICH WOULD BE CLASSIFIED AS A |
| PLACE OF ASSEMBLY PER NFPA. PLEASE CORRECT AND CLARIFY |
| THE OCCUPANCY TYPE AND OCCUPANT LOAD CALCULATIONS SO |
| THAT A PROPER CODE REVIEW MAY BE CONDUCTED. NFPA 1, |
| 1.14 |
| |
| (2) THE PLAN INDICATES THE BUILDING HAS AN EXISTING |
| FIRE SPRINKLER SYSTEM. THE SYSTEM MAY REQUIRE |
| MODIFICATION TO PROVIDE 100% COVERAGE INCLUDING INSIDE |
| THE WALK-IN COOLER. ANY AND ALL FIRE SPRINKLER WORK |
| WILL REQUIRE SEPARATE PERMITS AND SHOP DRAWINGS. |
| |
| (3) PROVIDE A DOOR SCHEDULE WITH THE TYPE OF HARDWARE |
| TO BE USED FROM THE SIDE OF EGRESS PER THE CORRECT |
| OCCUPANCY CLASSIFICATION, INCLUDING THE WALK-IN COOLER. |
| |
| (4) INDICATE THE MEANS OF EGRESS FOR THE WALK-IN COOLER |
| AND OCCUPIED SPACES AND INCLUDE MARKING THE MEANS OF |
| EGRESS AND EMERGENCY LIGHTING FOR THE SPACE. |
| |
| (5) THE MECHANICAL HOOD WILL REQUIRE SEPARATE PERMIT |
| SUBMITTAL AND APPROVAL. |
| |
| (6) THE HOOD FIRE SUPPRESSION SYSTEM WILL REQUIRE A |
| SEPARATE PERMIT SUBMITTAL AND APPROVAL. |
| |
| (7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| (8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RESUBMITTAL OF THE ABOVE. |
| |