Plan Review Notes
Plan Review Notes For Permit 22070634
Permit Number 22070634
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-07-21 12:59:44FIRE REVIEW COMMENTS:
  
 (1) SHEET S-1 INDICATES A BUSINESS OCCUPANCY WITH 41
 TOTAL OCCUPANCY. PER NFPA 101 THIS WOULD BE DEFINED AS
 A MERCANTILE OCCUPANCY. SHEET LS-1 INDICATES AN
 OCCUPANT LOAD OF 78, WHICH WOULD BE CLASSIFIED AS A
 PLACE OF ASSEMBLY PER NFPA. PLEASE CORRECT AND CLARIFY
 THE OCCUPANCY TYPE AND OCCUPANT LOAD CALCULATIONS SO
 THAT A PROPER CODE REVIEW MAY BE CONDUCTED. NFPA 1,
 1.14
  
 (2) THE PLAN INDICATES THE BUILDING HAS AN EXISTING
 FIRE SPRINKLER SYSTEM. THE SYSTEM MAY REQUIRE
 MODIFICATION TO PROVIDE 100% COVERAGE INCLUDING INSIDE
 THE WALK-IN COOLER. ANY AND ALL FIRE SPRINKLER WORK
 WILL REQUIRE SEPARATE PERMITS AND SHOP DRAWINGS.
  
 (3) PROVIDE A DOOR SCHEDULE WITH THE TYPE OF HARDWARE
 TO BE USED FROM THE SIDE OF EGRESS PER THE CORRECT
 OCCUPANCY CLASSIFICATION, INCLUDING THE WALK-IN COOLER.
  
 (4) INDICATE THE MEANS OF EGRESS FOR THE WALK-IN COOLER
 AND OCCUPIED SPACES AND INCLUDE MARKING THE MEANS OF
 EGRESS AND EMERGENCY LIGHTING FOR THE SPACE.
  
 (5) THE MECHANICAL HOOD WILL REQUIRE SEPARATE PERMIT
 SUBMITTAL AND APPROVAL.
  
 (6) THE HOOD FIRE SUPPRESSION SYSTEM WILL REQUIRE A
 SEPARATE PERMIT SUBMITTAL AND APPROVAL.
  
 (7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 (8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RESUBMITTAL OF THE ABOVE.
  