2022-07-22 16:26:23 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22070617 |
| 7/22/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS P4 & P5: PROVIDE A PLUMBING FIXTURE SCHEDULE- |
| SECS. 404, 419, 422, & 425 FBC P. |
| |
| 2) P4 & P5: NEW SINKS IN THE WORK ROOM AND LAB ARE |
| SHOWN. PLEASE CLARIFY THE USE OF THE SINKS AND WHAT THE |
| CONTENT OF THE DRAINAGE WILL BE. REFER TO SEC. 803.1 |
| FBC P- INDIRECT WASTE RECEPTORS AND CHEMICAL DILUTION |
| OR NEUTRALIZING DEVICES MAY BE REQUIRED. |
| |
| 3) P4 & P5: HOT WATER SHALL BE DELIVERED FROM THE SINKS |
| IN THE WORK ROOM AND LAB- SEC. 607.1 FBC P. THE PLANS |
| INDICATE COLD WATER SUPPLY ONLY TO TWO OF THE THREE |
| SINKS SHOWN IN THE LAB, AND THE WATER HEATER PIPING |
| DETAIL INDICATES ONLY TEMPERED WATER SUPPLY WILL BE |
| PROVIDED TO THE OTHER SINKS. PLEASE NOTE THAT TEMPERED |
| WATER SHALL BE DELIVERED FROM THE LAVATORIES, HOWEVER |
| HOT WATER AT A MINIMUM TEMPERATURE OF 110 DEGREES F |
| SHALL BE DELIVERED FROM THE OTHER SINKS INCLUDING THE |
| MOP SINK REFERENCED IN THE WATER HEATER DETAIL. PLEASE |
| IDENTIFY THE MOP SINK LOCATION ON THE PLANS. |
| |
| 4) P4 & P5: REFER TO SEC. 411.1 FBC P- IF AN EMERGENCY |
| SHOWER AND EYE WASH STATION ARE REQUIRED BY OSHA OR |
| OTHER GOVERNING AGENCIES, THE FIXTURES SHALL CONFORM TO |
| ISEA Z358.1. IF APPLICABLE THE PLANS SHALL BE REVISED |
| AND MANUFACTURER'S SPECIFICATIONS SHALL BE SUBMITTED. |
| |
| 5) P4 & P5: PROVIDE EQUIPMENT SCHEDULES FOR THE |
| 47-GALLON STORAGE WATER HEATER AND THE TANKLESS WATER |
| HEATERS SHOWN AT THE LAVATORIES- SEC. 502.1 FBC P AND |
| C404.2 FBC EC. |
| |
| 6) P4 & P5: SHOW THE MEANS OF TRAP SEAL PROTECTION FOR |
| THE FLOOR DRAINS- SEC. 1002.4.1 FBC P. REFER TO COMMENT |
| #2 ABOVE AND INDICATE THE CONTENT OF THE DRAINAGE BEING |
| CONVEYED TO THE SANITARY SYSTEM FROM THE FLOOR DRAINS. |
| |
| 7) P4 & P5: PROVIDE AN ENLARGED DETAIL SHOWING THE |
| WATER SUPPLY CONNECTION TO THE FILTRATION EQUIPMENT AND |
| LOCATION OF THE BACKFLOW PREVENTER- SEC. 608.3 FBC P. |
| |
| 8) A3 & P4: PROVIDE PLUMBING FIXTURE CALCULATIONS FOR |
| THE OCCUPANCY IN COMPLIANCE WITH TABLE 403.1 FBC P. |
| INDICATE THE REQUIRED AND PROVIDED NUMBER OF FIXTURES |
| BASED ON THE TABLE. |
| |
| 9) A3 & P4: IDENTIFY THE TOILET ROOMS AS MALE, FEMALE, |
| OR UNISEX- SEC. 403.4 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |