2022-07-18 14:42:22 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION OF CONCRETE RESTORATION |
| HOWEVER, THERE IS NO INDICATIOS OF WHERE THIS WORK IS |
| LOCATED. |
| |
| PER NFPA 1 |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS. |
| |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOR PLAN |
| SHEET(S) INDICATING WHERE THE REPAIRS WILL BE. |
| |
| |
| |
| 1A) THERE ARE NO INDICATIONS IF THE REPAIRS WILL IMPACT |
| THE MEANS OF EGRESS AND/OR IF THE BUILDING WILL BE |
| OCCUPIED DURING THE REPAIR PROCESS. |
| |
| PER NFPA 1 |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| |
| 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| |
| PLEASE PROVIDE A LIFE SAFETY REVIEW ENSURING THE MEANS |
| OF EGRESS IS NOT COMPROMISED AND, IF APPLICABLE, |
| ALTERNATIVE EGRESS ROUTES ARE WELL DEFINED. |
| |
| |
| 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |