Plan Review Notes For Permit 22070587 |
Permit Number |
22070587 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2022-09-01 14:12:04 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | FROM PREVIOUS LIST: | | | | TEST REPORTS FOR BOTH MSC90 AND SUPERSIM90 WERE | | SUBMITTED, LVT FLOORING. | | | | THE FLAME SPREAD WAS FOR SUPERSIM 90 WITH A TILE FLOOR, | | NEED A FLAME SPREAD WITH A COMBUSTIBLE FLOOR OR NO | | FLOORING.\ | | | | MSC90 STC/IIC TEST REPORTS USE AN 8" SLAB, HOW HAVE YOU | | DETERMINED THAT THIS BUILDING HAS 8" FLOORS? | | | | PROFLEX MAKES A PRODUCT FOR THIS APPLICATION, LV200. IF | | YOU WOULD LIKE TO USE THIS PRODUCT PLEASE INDICATE THAT | | WHEN RESUBMITTING AND THE TEST REPORTS WILL BE UPLOADED | | FOR YOU. | | | | SEE PREVIOUS REVIEWS FOR CODE REFERENCES. |
|