| 22070563 1501 S FLAGLER DR # 2B |
| |
| 1ST REVIEW |
| |
| PLUMBING COMMENTS: DENIED |
| |
| 1. PER WPB FBC 107.2.1, PROVIDE A CROSS-SECTION SHOWER |
| WALL/FLOOR/DRAIN AND THRESHOLD DETAIL |
| DETAIL SHALL INCLUDE ALL COMPONENTS OF FBC PL 421.5.2 |
| AS FOLLOWS: |
| LINERS SHALL TURN UP ON ALL SIDES NOT LESS THAN 2 |
| INCHES ABOVE THE FINISHED THRESHOLD LEVEL |
| LINERS SHALL BE RECESSED AND FASTENED TO AN APPROVED |
| BACKING |
| LINERS SHALL NOT BE NAILED OR PERFORATED AT ANY POINT |
| LESS THAN 1 INCH ABOVE THE FINISHED THRESHOLD |
| LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12 |
| UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED |
| TOWARD THE FIXTURE DRAIN |
| LINERS SHALL BE SECURELY FASTENED TO THE WASTE OUTLET |
| AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT JOINT |
| BETWEEN THE LINER AND THE OUTLET |
| FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE |
| LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY |
| SOUND BASE. |
| SPECIFY LINER MATERIAL COMPLYING WITH ONE OF THE |
| FOLLOWING FBC PL SECTIONS-421.5.2.1, 421.5.2.2, |
| 421.5.2.3, 421.5.2.4, 421.5.2.5 OR 421.5.2.6. NOTE THAT |
| FBC PL 421.5.2.1 PLASTICIZED POLYVINYL CHLORIDE (PVC) |
| SHEETS MEETING THE REQUIREMENTS OF ASTM D4551 IS A |
| COMMON LINER USED. |
| FBC PL 421.4.1 BATHTUB FLOORS, SHOWER FLOORS, WALL |
| AREAS ABOVE BUILT-IN TUBS THAT HAVE INSTALLED SHOWER |
| HEADS AND WALLS IN SHOWER COMPARTMENTS SHALL BE |
| CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND |
| NONABSORBENT WATERPROOF MATERIALS. WALL MATERIALS SHALL |
| EXTEND TO A HEIGHT OF NOT LESS THAN 6 ABOVE THE ROOM |
| FLOOR LEVEL, AND NOT LESS THAN 70 INCHES ABOVE THE |
| DRAIN OF THE TUB OR SHOWER. SUCH WALLS SHALL FORM A |
| WATER-TIGHT JOINT WITH EACH OTHER AND WITH EITHER THE |
| TUB OR SHOWER FLOOR. |
| |
| 2. PER FBC PL 412.3INDIVIDUAL SHOWER AND TUB-SHOWER |
| COMBINATION VALVES SHALL BE BALANCED-PRESSURE, |
| THERMOSTATIC OR COMBINATION |
| BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO |
| THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA |
| B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE |
| INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER |
| COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE |
| EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF |
| THE VALVE TO 120?F (49?C), WHICH SHALL BE FIELD |
| ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S |
| INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE |
| UTILIZED FOR COMPLIANCE WITH THIS SECTION. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |