2022-07-19 05:43:50 | SHEET FA-1A INDICATES THERE WILL BE IN-DUCT SMOKE |
| DETECTORS ON THE 1ST AND 2ND LEVELS OF THIS STRUCTURE |
| BUT I DO NOT SEE THEM IN THE MECHANICAL ROOMS ON SHEET |
| FA-2. |
| ALSO SEE THE FIRE REVIEW COMMENTS BELOW. |
| |
| THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| |
| 1) THERE ARE INDICATIONS OF UNIT SMOKE ALARMS THAT ARE |
| INTERCONNECTED WITH OTHER UNIT SMOKE ALARMS THROUGHT |
| THE ENTIRE FLOOR. |
| |
| PER NFPA 101 CH 9 |
| |
| 9.6.2.10.9* IN NEW CONSTRUCTION, WHERE TWO OR MORE |
| SMOKE ALARMS ARE |
| REQUIRED WITHIN A DWELLING UNIT, SUITE OF ROOMS, OR |
| SIMILAR AREA, THEY |
| SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE ALARM |
| SHALL CAUSE THE |
| ALARM IN ALL SMOKE ALARMS WITHIN THE DWELLING UNIT, |
| SUITE OF ROOMS, OR |
| SIMILAR AREA TO SOUND, UNLESS OTHERWISE PERMITTED BY |
| ONE OF THE |
| FOLLOWING: |
| (1) THE REQUIREMENT OF 9.6.2.10.9 SHALL NOT APPLY WHERE |
| PERMITTED BY |
| ANOTHER SECTION OF THIS CODE. |
| (2) THE REQUIREMENT OF 9.6.2.10.9 SHALL NOT APPLY TO |
| CONFIGURATIONS |
| THAT PROVIDE EQUIVALENT DISTRIBUTION OF THE ALARM |
| SIGNAL |
| |
| PLEASE REVIEW AND PROVIDE CLARIFICATION THAT THESE |
| SMOKE ALARMS WILL BE INTERCOONECTED AND SOUND ONLY IN |
| THE UNIT AND NOT IN EACH UNIT ON THE ENTIRE |
| FLOOR/BUILDING. |
| |
| |
| |
| 2) THERE ARE INDICATIONS OF UNIT SMOKE ALARMS THAT ARE |
| INSTALLED IN CLOSE PROXIMITY OF A BATHROOM DOOR. |
| |
| 9.6.2.10.6* SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT |
| BE INSTALLED WITHIN A 36 IN. (910 MM) HORIZONTAL PATH |
| FROM A DOOR TO A BATHROOM |
| CONTAINING A SHOWER OR TUB UNLESS LISTED FOR |
| INSTALLATION IN CLOSE PROXIM ITY TO SUCH LOCATIONS. |
| |
| PLEASE REVIEW AND PROVIDE CLARIFICATION THAT THESE |
| SMOKE ALARMS ARE LOCATED PER THE REQUIREMENT AND WILL |
| NOT LEAD TO FALSE ALARMS DUE TO STEAM. |
| |
| |
| 3) THERE ARE INDICATIONS OF UNIT SMOKE ALARMS THAT DO |
| NOT APPEAR TO MET THE SA LOCATION REQUIREMENTS OF "THE |
| IMMEDIATE VICINITY OF BEDROOMS. |
| |
| 30.3.4.5* SMOKE ALARMS. SMOKE ALARMS SHALL BE INSTALLED |
| IN ACCOR DANCE WITH 9.6.2.10 IN EVERY SLEEPING AREA, |
| OUTSIDE EVERY SLEEPING AREA |
| IN THE IMMEDIATE VICINITY OF THE BEDROOMS, AND ON ALL |
| LEVELS OF THE DWELLING UNIT, INCLUDING BASEMENTS. |
| |
| PLEASE REVIEW AND PROVIDE CLARIFICATION THAT THESE |
| SMOKE ALARMS ARE LOCATED PER THE REQUIREMENT. |
| |
| |
| |
| 4) THERE ARE INDICATIONS OF UNIT SMOKE ALARMS THAT DO |
| NOT APPEAR TOO CLOSE TO THE KITCHEN. |
| |
| THOUGH THERE IS A STATEMENT THAT THE STOVE HAS BEEN |
| REMOVED FROM THE UNITS, THER STILL BE ISSUES WITH |
| MICROWAVE OVERHEATED FOODS, TOSTER/TOASTER OVENS, |
| HOTPLATES, ETC. |
| |
| 9.6.2.10.4* UNLESS OTHERWISE PROVIDED IN 9.6.2.10.6, |
| SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE INSTALLED |
| WITHIN AN AREA OF EXCLUSION DETER MINED BY A 10 FT (3.0 |
| M) |
| RADIAL DISTANCE ALONG A HORIZONTAL FLOW PATH FROM A |
| STATIONARY OR FIXED COOKING APPLIANCE, UNLESS LISTED |
| FOR INSTALLATION IN CLOSE PROXIMITY TO COOKING |
| APPLIANCES. SMOKE ALARMS AND SMOKE |
| DETECTORS INSTALLED BETWEEN 10 FT (3.0 M) AND 20 FT |
| (6.1 M) ALONG A HORI ZONTAL FLOW PATH FROM A STATIONARY |
| OR FIXED COOKING APPLIANCE SHALL BE EQUIPPED WITH AN |
| ALARM-SILENCING MEANS OR USE PHOTOELECTRIC DETECTION |
| |
| PLEASE REVIEW AND PROVIDE POSSIBLE ALTERNATIVE |
| LOCATIONS THAT STILL MEET THE COVERAGE REQUIREMENTS. |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |