Plan Review Notes
Plan Review Notes For Permit 22070495
Permit Number 22070495
Review Stop M
Sequence Number 1
Notes
Date Text
2022-07-19 05:43:50SHEET FA-1A INDICATES THERE WILL BE IN-DUCT SMOKE
 DETECTORS ON THE 1ST AND 2ND LEVELS OF THIS STRUCTURE
 BUT I DO NOT SEE THEM IN THE MECHANICAL ROOMS ON SHEET
 FA-2.
 ALSO SEE THE FIRE REVIEW COMMENTS BELOW.
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 1) THERE ARE INDICATIONS OF UNIT SMOKE ALARMS THAT ARE
 INTERCONNECTED WITH OTHER UNIT SMOKE ALARMS THROUGHT
 THE ENTIRE FLOOR.
  
 PER NFPA 101 CH 9
  
 9.6.2.10.9* IN NEW CONSTRUCTION, WHERE TWO OR MORE
 SMOKE ALARMS ARE
 REQUIRED WITHIN A DWELLING UNIT, SUITE OF ROOMS, OR
 SIMILAR AREA, THEY
 SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE ALARM
 SHALL CAUSE THE
 ALARM IN ALL SMOKE ALARMS WITHIN THE DWELLING UNIT,
 SUITE OF ROOMS, OR
 SIMILAR AREA TO SOUND, UNLESS OTHERWISE PERMITTED BY
 ONE OF THE
 FOLLOWING:
 (1) THE REQUIREMENT OF 9.6.2.10.9 SHALL NOT APPLY WHERE
 PERMITTED BY
 ANOTHER SECTION OF THIS CODE.
 (2) THE REQUIREMENT OF 9.6.2.10.9 SHALL NOT APPLY TO
 CONFIGURATIONS
 THAT PROVIDE EQUIVALENT DISTRIBUTION OF THE ALARM
 SIGNAL
  
 PLEASE REVIEW AND PROVIDE CLARIFICATION THAT THESE
 SMOKE ALARMS WILL BE INTERCOONECTED AND SOUND ONLY IN
 THE UNIT AND NOT IN EACH UNIT ON THE ENTIRE
 FLOOR/BUILDING.
  
  
  
 2) THERE ARE INDICATIONS OF UNIT SMOKE ALARMS THAT ARE
 INSTALLED IN CLOSE PROXIMITY OF A BATHROOM DOOR.
  
 9.6.2.10.6* SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT
 BE INSTALLED WITHIN A 36 IN. (910 MM) HORIZONTAL PATH
 FROM A DOOR TO A BATHROOM
 CONTAINING A SHOWER OR TUB UNLESS LISTED FOR
 INSTALLATION IN CLOSE PROXIM ITY TO SUCH LOCATIONS.
  
 PLEASE REVIEW AND PROVIDE CLARIFICATION THAT THESE
 SMOKE ALARMS ARE LOCATED PER THE REQUIREMENT AND WILL
 NOT LEAD TO FALSE ALARMS DUE TO STEAM.
  
  
 3) THERE ARE INDICATIONS OF UNIT SMOKE ALARMS THAT DO
 NOT APPEAR TO MET THE SA LOCATION REQUIREMENTS OF "THE
 IMMEDIATE VICINITY OF BEDROOMS.
  
 30.3.4.5* SMOKE ALARMS. SMOKE ALARMS SHALL BE INSTALLED
 IN ACCOR DANCE WITH 9.6.2.10 IN EVERY SLEEPING AREA,
 OUTSIDE EVERY SLEEPING AREA
 IN THE IMMEDIATE VICINITY OF THE BEDROOMS, AND ON ALL
 LEVELS OF THE DWELLING UNIT, INCLUDING BASEMENTS.
  
 PLEASE REVIEW AND PROVIDE CLARIFICATION THAT THESE
 SMOKE ALARMS ARE LOCATED PER THE REQUIREMENT.
  
  
  
 4) THERE ARE INDICATIONS OF UNIT SMOKE ALARMS THAT DO
 NOT APPEAR TOO CLOSE TO THE KITCHEN.
  
 THOUGH THERE IS A STATEMENT THAT THE STOVE HAS BEEN
 REMOVED FROM THE UNITS, THER STILL BE ISSUES WITH
 MICROWAVE OVERHEATED FOODS, TOSTER/TOASTER OVENS,
 HOTPLATES, ETC.
  
 9.6.2.10.4* UNLESS OTHERWISE PROVIDED IN 9.6.2.10.6,
 SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE INSTALLED
 WITHIN AN AREA OF EXCLUSION DETER MINED BY A 10 FT (3.0
 M)
 RADIAL DISTANCE ALONG A HORIZONTAL FLOW PATH FROM A
 STATIONARY OR FIXED COOKING APPLIANCE, UNLESS LISTED
 FOR INSTALLATION IN CLOSE PROXIMITY TO COOKING
 APPLIANCES. SMOKE ALARMS AND SMOKE
 DETECTORS INSTALLED BETWEEN 10 FT (3.0 M) AND 20 FT
 (6.1 M) ALONG A HORI ZONTAL FLOW PATH FROM A STATIONARY
 OR FIXED COOKING APPLIANCE SHALL BE EQUIPPED WITH AN
 ALARM-SILENCING MEANS OR USE PHOTOELECTRIC DETECTION
  
 PLEASE REVIEW AND PROVIDE POSSIBLE ALTERNATIVE
 LOCATIONS THAT STILL MEET THE COVERAGE REQUIREMENTS.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  