22070486 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-08-02 17:11:13 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. FBC R 4501.17, REVISE PLAN TO SHOW A CONTINUOUS | | BARRIER. IF USING AN EXISTING FENCE, NOTE ON PLAN. | | | | 2ND REVIEW, I WAS UNABLE TO LOCATE A PERMIT FOR THE | | "EXISTING FENCE". IT APPEARS THAT THIS FENCE IS NOT | | LOCATED ON THE SUBJECT PROPERTY. THE POOL BARRIER MUST | | BE ENTIRELY WITHIN THIS PROPERTY OWNER'S CONTROL. | | | | EITHER PROVIDE A PERMIT NUMBER FOR THE FENCE SHOWING IT | | IS LOCATED ON THE SUBJECT PROPERTY, OR REVISE PLAN TO | | SHOW COMPLIANCE. | | | | |
|