Plan Review Notes For Permit 22070410 |
Permit Number |
22070410 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-09-16 10:43:13 | PROVIDE A DETAIL OF THE DRYER DUCT AT THE RATED WALLS. | | IF THEY PENETRATE THE RATED WALLS THEY MUST BE IN A | | SHAFT ALL THE WAY TO THE EXTERIOR TERMINATION. FMC | | 504.2 | | | | 504.2 EXHAUST PENETRATIONS. WHERE A CLOTHES DRYER | | EXHAUST | | DUCT PENETRATES A WALL OR CEILING MEMBRANE, THE ANNULAR | | SPACE | | SHALL BE SEALED WITH NONCOMBUSTIBLE MATERIAL, APPROVED | | FIRE | | CAULKING OR A NONCOMBUSTIBLE DRYER EXHAUST DUCT WALL | | RECEPTACLE. | | DUCTS THAT EXHAUST CLOTHES DRYERS SHALL NOT PENETRATE | | OR | | BE LOCATED WITHIN ANY FIREBLOCKING, DRAFTSTOPPING OR | | ANY WALL, | | FLOOR/CEILING OR OTHER ASSEMBLY REQUIRED BY THE FLORIDA | | BUILDING | | CODE, BUILDING TO BE FIRE-RESISTANCE RATED, UNLESS SUCH | | DUCT IS CONSTRUCTED OF GALVANIZED STEEL OR ALUMINUM OF | | THE | | THICKNESS SPECIFIED IN SECTION 603.4 AND THE | | FIRE-RESISTANCE | | RATING IS MAINTAINED IN ACCORDANCE WITH THE FLORIDA | | BUILDING | | CODE, BUILDING. FIRE DAMPERS, COMBINATION FIRE/SMOKE | | DAMPERS | | AND ANY SIMILAR DEVICES THAT WILL OBSTRUCT THE EXHAUST | | FLOW | | SHALL BE PROHIBITED IN CLOTHES DRYER EXHAUST DUCTS. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|