Plan Review Notes
Plan Review Notes For Permit 22070410
Permit Number 22070410
Review Stop E
Sequence Number 1
Notes
Date Text
2022-08-15 15:57:36ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE CLARITY ON THE ELECTRIC WORKSCOPE.
 PLEASE DETAIL WHICH UNITS WILL BE INCLUDED IN THE WORK
 AND THE EXTENT OF THE WORK. IE. WILL ALL THE UNITS BE
 REMODELED? TO WHAT EXTENT, DO THE SUBMITTED DRAWINGS
 DETAIL NEW WIRING OR IS THIS WIRING EXISTING? THE
 ELECTRICAL DRAWINGS DETAIL A 400-AMP EXISTING SERVICE
 AND A NEW PROPOSED 600-AMP SERVICE. WILL THIS BE A
 COMPLETE NEW ELECTRIC SERVICE? THE COVER SHEET STATES
 ONLY ELECTRIC SWITCHES AND RECEPTACLES ARE TO BE
 REPLACED. ON THE FLOOR PLAN, TWO UNITS ARE GRAYED OUT,
 ARE THESE NOT INCLUDED? PLEASE PROVIDE AN ACURRATE WORK
 SCOPE AND ALL APPLICABLE DRAWINGS. FBC 107.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  