2022-08-15 15:57:36 | ELECTRIC REVIEW FAILED | | 1) PLEASE PROVIDE CLARITY ON THE ELECTRIC WORKSCOPE. | | PLEASE DETAIL WHICH UNITS WILL BE INCLUDED IN THE WORK | | AND THE EXTENT OF THE WORK. IE. WILL ALL THE UNITS BE | | REMODELED? TO WHAT EXTENT, DO THE SUBMITTED DRAWINGS | | DETAIL NEW WIRING OR IS THIS WIRING EXISTING? THE | | ELECTRICAL DRAWINGS DETAIL A 400-AMP EXISTING SERVICE | | AND A NEW PROPOSED 600-AMP SERVICE. WILL THIS BE A | | COMPLETE NEW ELECTRIC SERVICE? THE COVER SHEET STATES | | ONLY ELECTRIC SWITCHES AND RECEPTACLES ARE TO BE | | REPLACED. ON THE FLOOR PLAN, TWO UNITS ARE GRAYED OUT, | | ARE THESE NOT INCLUDED? PLEASE PROVIDE AN ACURRATE WORK | | SCOPE AND ALL APPLICABLE DRAWINGS. FBC 107.2 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|