2022-07-13 12:34:16 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| PERMIT- 22070329 |
| 7/13/2022 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P601: THE GAS RISER IS INCOMPLETE. REFER TO |
| SECS. G2412.3 & G2412.4 FBC RES AND PROVIDE A COMPLETE |
| GAS RISER THAT INCLUDES THE FOLLOWING INFORMATION: |
| A) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| B) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| F) LOCATIONS OF LOW PRESSURE REGULATORS. |
| G) OUTLET PRESSURES AT REGULATORS. |
| H) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| I) PIPE SIZING TABLES. |
| |
| 2) SHEETS P301 & P601: PROVIDE COMBUSTION AIR |
| CALCULATIONS FOR THE NEW RANGE AND INDICATE HOW THE AIR |
| WILL BE PROVIDED- SEC. G2407.1 FBC RES. |
| |
| 3) THE GAS RISER SHALL BEAR THE PRINTED NAME, LICENSE |
| NUMBER AND THE SIGNATURE OF THE CONTRACTOR OR QUALIFIER |
| WHO PREPARED THE DRAWING- SEC. 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |