2022-07-11 15:10:571ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22070192
 7/11/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLANS INDICATE A PARTIAL DEMOLITION. CLARIFY IF
 THE WATER METER AND UTILITY ACCOUNT WILL REMAIN IN
 PLACE AND ACTIVE, AND IF THE EXISTING BUILDING DRAIN
 AND SEWER LINE WILL REMAIN. IF THE METER IS TO BE
 PULLED PLEASE SUBMIT A REQUEST TO THE WPB UTILITIES
 DEPT. ON THEIR FORM, AND A UTILITY RELEASE FORM. IF THE
 METER IS TO REMAIN AND THE WATER SERVICE IS TO BE USED
 DURING DEMOLITION, PLEASE NOTE A BACKFLOW PREVENTION
 DEVICE IS REQUIRED ON THE SERVICE AND A PERMIT IS
 REQUIRED FOR THE DEVICE. THE PLUMBING DEMOLITION PERMIT
 WILL BE APPROVED AFTER THE BACKFLOW PERMIT IS APPROVED.
 PLEASE SEE THE BUILDING REVIEW COMMENTS FOR FURTHER
 INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  