2023-03-03 16:09:56 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22070156 |
| 3/3/23 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE PERMIT APPLICATION HAS THESE ERRORS: |
| A) SUB-PERMIT IS CHECKED- THIS IS A PRIMARY PERMIT. |
| B) PRIMARY PERMIT NUMBER IS NOT 22070156. THE PRIMARY |
| PERMIT IS 19120499. |
| C) OWNER INFORMATION AND PCN NOT PROVIDED. |
| |
| 2) PROVIDE A PLUMBING PLAN SHOWING THE PIPING RUN FROM |
| THE BUILDING TO THE GREASE INTERCEPTOR- SEC. 107.2.1 |
| WPB. PLEASE PROVIDE ON THE PLAN THE FOLLOWING ITEMS PER |
| FBC P. |
| |
| A) EQUIPMENT SCHEDULE INDICATING THE MAKE, AND MODEL |
| AND CAPACITY OF THE UNIT- SEC. 1003.3.5. |
| |
| B) SIZING CALCULATIONS IN ACCORDANCE WITH ASME |
| A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3, |
| OR PDI G101 FOR HYDROMECHANICAL TYPES- SEC.1003.5.1. |
| |
| C) AN ENLARGED PIPING DIAGRAM OR ISOMETRIC SHOWING THE |
| SIZES OF INLETS, OUTLETS, CLEANOUTS, AND VENTS- SEC. |
| 107.3.5.1.3 WPB. PLEASE INCLUDE A DETAIL FOR THE |
| CLEANOUT WHICH WILL BE USED AS THE SAMPLING PORTBY THE |
| WPB UTILITIES DEPT. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |