2022-10-11 20:53:19 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| |
| 1. PER YOUR REPSONSE LETTER THE OVERHEAD SERVICE |
| CONDUCTORS ARE "EXISTING". REGARDLESS THAT OVERHEAD |
| SERVICE ENTRANCE CONDUCTORS ARE EXISTING YOU ARE |
| PROPOSING AN INCREASED SERVICE SIZE FROM 400AMPS TO |
| 600AMPS. OVERHEAD SERVICE ENTRANCE CONDUCTORS AND |
| CONDUIT MUST BE OF SUFFICENT SIZE. NEC 230.23A FBC |
| 107.2.1 |
| |
| 2. SERVICE ENTRANCE CONDUCTORS FROM METER TO SERVICE |
| DISCONNECT ARE NOT OF SUFFICIENT SIZE FOR A 600AMP |
| SERVICE. NEC 230.31 |
| |
| 3. NO EQUIPMENT GROUNDING CONDUCTOR PERMITTED FROM |
| METER-CAN TO SERVICE DISCONNECTING MEANS. THIS IS A |
| PARRALLEL PATH BACK TO THE GROUNDED CONDUCTOR (NEUTRAL) |
| PLEASE REMOVE EQUIPMENT GROUND, THE EQUIPMENT GROUNDING |
| CONDUCTOR ORIGINATES ON THE LOAD SIDE OF THE SERVICE |
| DISCONNECTING MEANSNEC 250.24 |
| |
| |
| 4. PARALLELL CONDUCTORS TO METER CENTER (UNGROUNDED |
| CONDUCTORS, GROUNDED CONDUCTORS, AND EQUIPMENT |
| GROUNDING CONDUCTORS) ARE NOT OF SUFFICENT SIZE FOR |
| 600AMP PARALLEL FEEDERS. |
| NEC 215.2 NEC 240.4 NEC 310.10H NEC 250.122 |
| |
| 5. NO OVERCURRENT PROTECTION SHOWN FOR UNIT BREAKERS ON |
| METER CENTER. FBC 107.2.1 |
| |
| 6. WHAT IS METER CENTER AMPERAGE/VOLTAGE/PHASE RATING? |
| FBC 107.2.1 |
| |
| 7. WHAT IS VOLTAGE AND PHASE OF SERVICE? NOT LABELED ON |
| PLAN. SINGLE PHASE? THREE PHASE? |
| |
| 8. HOUSE PANEL IS SHOWN AS 100AMPS BUT ON PANEL |
| SCHEDULE IT'S SHOWN AS A 60AMP MAIN BREAKER PANEL. |
| PROVIDE CORRECTION/CLARIFICATION FBC 107.2.1 |
| |
| 9. THERE IS A BRANCH CIRCUIT FROM HOUSE PANEL THAT |
| SHOWS A SINGLE #3 CU CONDUCTOR IN A 1/4'' CONDUIT??? |
| THERE IS NO 1/4'' CONDUIT PERMITTED AND A SINGLE #3 CU |
| CONDUCTOR IS NOT A COMPLETE BRANCH CIRCUIT. PROVIDE |
| CORRECTION. |
| |
| 10. **** PREVIOUS PLAN REVIEW COMMENT SATISFIED |
| |
| 11. WHAT WIRE TYPE IN UNITS IS BEING PROPSOED? MC? |
| ROMEX? FBC 107.2.1 |
| |
| 12. SMOKE ALARMS MUST BE 3 FT AWAY FROM TIPS OF FAN |
| BLADES, BATHROOM DOORS, FORCED AIR, AND 10FT AWAY FROM |
| COOKING EQUIPMENT PER NFPA 72. PROVIDE CORRECTIONS. |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| CELL: 561-805-6744 |
| |
| |