Plan Review Notes
Plan Review Notes For Permit 22070126
Permit Number 22070126
Review Stop E
Sequence Number 3
Notes
Date Text
2022-10-11 20:53:19ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
  
 1. PER YOUR REPSONSE LETTER THE OVERHEAD SERVICE
 CONDUCTORS ARE "EXISTING". REGARDLESS THAT OVERHEAD
 SERVICE ENTRANCE CONDUCTORS ARE EXISTING YOU ARE
 PROPOSING AN INCREASED SERVICE SIZE FROM 400AMPS TO
 600AMPS. OVERHEAD SERVICE ENTRANCE CONDUCTORS AND
 CONDUIT MUST BE OF SUFFICENT SIZE. NEC 230.23A FBC
 107.2.1
  
 2. SERVICE ENTRANCE CONDUCTORS FROM METER TO SERVICE
 DISCONNECT ARE NOT OF SUFFICIENT SIZE FOR A 600AMP
 SERVICE. NEC 230.31
  
 3. NO EQUIPMENT GROUNDING CONDUCTOR PERMITTED FROM
 METER-CAN TO SERVICE DISCONNECTING MEANS. THIS IS A
 PARRALLEL PATH BACK TO THE GROUNDED CONDUCTOR (NEUTRAL)
 PLEASE REMOVE EQUIPMENT GROUND, THE EQUIPMENT GROUNDING
 CONDUCTOR ORIGINATES ON THE LOAD SIDE OF THE SERVICE
 DISCONNECTING MEANSNEC 250.24
  
  
 4. PARALLELL CONDUCTORS TO METER CENTER (UNGROUNDED
 CONDUCTORS, GROUNDED CONDUCTORS, AND EQUIPMENT
 GROUNDING CONDUCTORS) ARE NOT OF SUFFICENT SIZE FOR
 600AMP PARALLEL FEEDERS.
 NEC 215.2 NEC 240.4 NEC 310.10H NEC 250.122
  
 5. NO OVERCURRENT PROTECTION SHOWN FOR UNIT BREAKERS ON
 METER CENTER. FBC 107.2.1
  
 6. WHAT IS METER CENTER AMPERAGE/VOLTAGE/PHASE RATING?
 FBC 107.2.1
  
 7. WHAT IS VOLTAGE AND PHASE OF SERVICE? NOT LABELED ON
 PLAN. SINGLE PHASE? THREE PHASE?
  
 8. HOUSE PANEL IS SHOWN AS 100AMPS BUT ON PANEL
 SCHEDULE IT'S SHOWN AS A 60AMP MAIN BREAKER PANEL.
 PROVIDE CORRECTION/CLARIFICATION FBC 107.2.1
  
 9. THERE IS A BRANCH CIRCUIT FROM HOUSE PANEL THAT
 SHOWS A SINGLE #3 CU CONDUCTOR IN A 1/4'' CONDUIT???
 THERE IS NO 1/4'' CONDUIT PERMITTED AND A SINGLE #3 CU
 CONDUCTOR IS NOT A COMPLETE BRANCH CIRCUIT. PROVIDE
 CORRECTION.
  
 10. **** PREVIOUS PLAN REVIEW COMMENT SATISFIED
  
 11. WHAT WIRE TYPE IN UNITS IS BEING PROPSOED? MC?
 ROMEX? FBC 107.2.1
  
 12. SMOKE ALARMS MUST BE 3 FT AWAY FROM TIPS OF FAN
 BLADES, BATHROOM DOORS, FORCED AIR, AND 10FT AWAY FROM
 COOKING EQUIPMENT PER NFPA 72. PROVIDE CORRECTIONS.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  