2022-08-10 19:51:50 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| THERE ARE SEVERAL MAJOR CODE VIOLATIONS ON THIS PLAN. |
| THE PLAN REVIEW HAS BEEN STOPPED. PLEASE KEEP IN MIND |
| WHEN RESUBMITTING ADDITIONAL VIOLATIONS MAY BE NOTED. |
| PLEASE LOOK OVER ENTIRE PLAN BEFORE RESUBMITTING. |
| |
| |
| 1. WRONG SERVICE ENTRANCE CONDUCTOR SIZE, ARE YOU |
| PROPOSING 2 SETS OR 4-300MCM CU COPPER FOR THE SERVICE |
| MAST? IF SO PLEASE BE MORE CLEAR. NEC 230.23A FBC |
| 107.2.1 |
| |
| 2. 3/4'' CONDUIT NIPPLES TOO SMALL TO METER CENTER FOR |
| FEEDERS, HOW MANY SETS OF PARALLEL FEEDERS ARE YOU |
| PROPOSING? AGAIN PLAN IS NOT CLEAR. NEC 300.17 FBC |
| 107.2.1 |
| |
| 3. NO NEUTRAL (GROUNDED CONDUCTOR) BROUGHT TO METER |
| CENTER NEC 215.2A2 |
| |
| 4. WIRES IN SERVICE MAST PER PLAN, 4-#300 CU AND 1-300 |
| CU NEUTRAL?? PLEASE EXPLAIN THE 5TH WIRE? |
| |
| 5. 3/4'' CONDUIT TO HOUSE PANEL IS TO SMALL AND HAS NO |
| NEUTRAL BROUGHT TO IT. NEC300.17 NEC215.A2 |
| |
| 6. SERVICE DISCONNECTING MEANS NOT SHOWN ON FLOOR PLAN |
| FBC 107.2.1 |
| |
| 7. TAMPERPROOF RECEPTACLES REQUIRED PER NEC 406.12 |
| |
| 8. AFCI PROTECTION REQUIRED PER NEC 210.12A AND B |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |