2022-08-10 19:51:50ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 THERE ARE SEVERAL MAJOR CODE VIOLATIONS ON THIS PLAN.
 THE PLAN REVIEW HAS BEEN STOPPED. PLEASE KEEP IN MIND
 WHEN RESUBMITTING ADDITIONAL VIOLATIONS MAY BE NOTED.
 PLEASE LOOK OVER ENTIRE PLAN BEFORE RESUBMITTING.
  
  
 1. WRONG SERVICE ENTRANCE CONDUCTOR SIZE, ARE YOU
 PROPOSING 2 SETS OR 4-300MCM CU COPPER FOR THE SERVICE
 MAST? IF SO PLEASE BE MORE CLEAR. NEC 230.23A FBC
 107.2.1
  
 2. 3/4'' CONDUIT NIPPLES TOO SMALL TO METER CENTER FOR
 FEEDERS, HOW MANY SETS OF PARALLEL FEEDERS ARE YOU
 PROPOSING? AGAIN PLAN IS NOT CLEAR. NEC 300.17 FBC
 107.2.1
  
 3. NO NEUTRAL (GROUNDED CONDUCTOR) BROUGHT TO METER
 CENTER NEC 215.2A2
  
 4. WIRES IN SERVICE MAST PER PLAN, 4-#300 CU AND 1-300
 CU NEUTRAL?? PLEASE EXPLAIN THE 5TH WIRE?
  
 5. 3/4'' CONDUIT TO HOUSE PANEL IS TO SMALL AND HAS NO
 NEUTRAL BROUGHT TO IT. NEC300.17 NEC215.A2
  
 6. SERVICE DISCONNECTING MEANS NOT SHOWN ON FLOOR PLAN
 FBC 107.2.1
  
 7. TAMPERPROOF RECEPTACLES REQUIRED PER NEC 406.12
  
 8. AFCI PROTECTION REQUIRED PER NEC 210.12A AND B
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH