Plan Review Notes
Plan Review Notes For Permit 22070126
Permit Number 22070126
Review Stop B
Sequence Number 1
Notes
Date Text
2022-08-17 14:51:26WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22070126
 ADD: 3012 BROADWAY
 CONT: PM DEVELOPMENT
 TEL: 561-889-5874
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 NOTES: 1) COVERSHEET SUBMITTED DATED 7/05/2022 IS FOR
 WINDOW/DOOR PERMIT 22060734 ONLY.
 2) COVERSHEET SUBMITTED DATE 7/12/2022 R-2 RESIDENTIAL
 APARTMENT BUILDING
  
 1ST REVIEW
 DATE: WED. AUUST 17TH/ 2022
 ACTION: DENIED
  
 COVERSHEET DATED (SUBMMITTED 7/12/2022). R2 RESIDENTIAL
 APARTMENT BUILDING:
 1) DEFERRED SUBMITTALS ARE DENIED, SOUND ABATEMENT IS
 AN CODE ISSUE THAT NEEDS TO BE ADDRESSED BEFORE PERMIT
 ISSUANCE, AS PER ASSISTANT B. O. RICHARD GATHRIGHT.
 BUILDING TYPE III-V HAVE A LOWER FLAME SPREAD THAN TYPE
 I-II BUILDINGS!!!
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD, TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2020 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2A) COVERSHEET SUBMITTAL DATE 7/12/2022 UNDER THE
 LISTING OF PROJECT DATA LIST THIS AS A LEVEL 1
 ALTERATION. PLEASE REVIEW THE SCOPING FOR LEVEL 2
 ALTERATIONS SECTION 504.1 2020 FBC EXISTING BUILDING
 CODE. THE RECONFIGURATION OR SPACE, THE ADDITION OR
 ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION
 OR EXTENSION OF ANY SYSTEM OR THE INSTALLATION OF ANY
 ADDITIONAL EQUIPMENT, LEVEL 2.
  
 2B) 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL
 NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3) COVERSHEET SUBMITTAL DATE 7/12/22/ SMOKE ALARMS
 703.2 IS FOR LEVEL 1. THIS IS A LEVEL 2 ALTERATION AND
 THE FIRE ALARMS NEED TO SHOW COMPLIANCE WITH THE 2020
 FBC-EXIST. CODE SECTION 804.4.1.6.AS REQUIRED BY THE
 FLORIDA FIRE PREVENTION CODE FOR EXISTING GROUP R-2.
  
 4) SHEET A-1:
 4A) THE 1ST FLOOR PLAN SHOWS THE END UNIT TO BE
 ACCESSIBLE, IT IS NOT CLEAR IF THE INTERIOR FLOOR LEVEL
 IS THE SAME HEIGHT AS THE CONCRETE SLAB ON THE EXTERIOR
 OR WITHIN ? INCH OF THE SAME HEIGHT. 2020 FBC-ACCESS.
 CODE CHANGES IN LEVEL 303.2 AND 303.3. WHERE CHANGES IN
 LEVEL ARE PERMITTED IN THE FLOOR OR GROUND SURFACES,
 THEY SHALL COMPLY WITH SECTION 303. SEE 303.1 & 303.2.
  
 4B) THE FLOOR PLAN OF THE ACCESSIBLE UNIT NEEDS TO SHOW
 A ELEVATION VIEW. THE KITCHEN SINK SHOWS A FORWARD
 APPROACH BUT NOT GOING UNDER THE SINK CABINET, A SIDE
 APPROACH DOES NOT WORK SINCE THE SINK IS AGAINST THE
 WALL. 2020 ACCESS CODE 606.2 CLEAR FLOOR SPACE. 606.5
 EXPOSED PIPES AND SURFACES. 606.3 HEIGHT. LAVATORIES
 AND SINKS SHALL BE INSTALLED WITH THE FRONT OF THE
 HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 4C) PLEASE PROVIDE ELEVATION VIEWS OF THE ACCESSIBLE
 RESTROOM TO SHOW COMPLIANCE WITH PLUMBING ELEMENTS AND
 ACCESSORIES, 2020 FBC-ACCESSIBILITY CODE CHAPTER 6.
  
 5) SHEET A-2 SHOWS THE NEW GUARDRAIL / HANDRAIL SYSTEM
 AT 36 INCHES. 2020 EXISTING BUILDING CODE. 801.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE 2020 FLORIDA BUILDING CODE, BUILDING. PLEASE
 REVIEW SECTION 1014.2 FOR THE HEIGHT REQUIREMENTS.
 PLEASE ALSO REVIEW SECTION 1014.16 HANDRAIL EXTENSIONS,
 PLEASE SHOW THE FULL LENGTH OF THE HANDRAIL, GUARDRAIL
 ASSEMBLY.
  
 6) SHEET A-2 SHOWS THE NEW GUARDRAIL / HANDRAIL SYSTEM
 AT 36 INCHES. 2020 EXISTING BUILDING CODE. 801.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE 2020 FLORIDA BUILDING CODE, BUILDING. 2020
 FBC-BUILD. CODE SECTION 1015.3 GUARDS SHALL NOT BE LESS
 THAN 42 INCHES IN HEIGHT HIGH MEASURED VERTICALLY FROM
 ON STAIRWAYS FROM THE LINE CONNECTING THE LEADING EDGE
 OF THE TREAD NOSING.
  
 7) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.22061353
  
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  