2022-08-17 14:51:26 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 22070126 |
| ADD: 3012 BROADWAY |
| CONT: PM DEVELOPMENT |
| TEL: 561-889-5874 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| NOTES: 1) COVERSHEET SUBMITTED DATED 7/05/2022 IS FOR |
| WINDOW/DOOR PERMIT 22060734 ONLY. |
| 2) COVERSHEET SUBMITTED DATE 7/12/2022 R-2 RESIDENTIAL |
| APARTMENT BUILDING |
| |
| 1ST REVIEW |
| DATE: WED. AUUST 17TH/ 2022 |
| ACTION: DENIED |
| |
| COVERSHEET DATED (SUBMMITTED 7/12/2022). R2 RESIDENTIAL |
| APARTMENT BUILDING: |
| 1) DEFERRED SUBMITTALS ARE DENIED, SOUND ABATEMENT IS |
| AN CODE ISSUE THAT NEEDS TO BE ADDRESSED BEFORE PERMIT |
| ISSUANCE, AS PER ASSISTANT B. O. RICHARD GATHRIGHT. |
| BUILDING TYPE III-V HAVE A LOWER FLAME SPREAD THAN TYPE |
| I-II BUILDINGS!!! |
| FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, |
| STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND |
| WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ |
| NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| |
| 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 1C) FLAME SPREAD, TYPE III-TYPE V CONSTRUCTION: |
| FBC-B-2020 720.2 CONCEALED INSTALLATION. INSULATING |
| MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF |
| ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD |
| INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX |
| OF NOT MORE THAN 450. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 2A) COVERSHEET SUBMITTAL DATE 7/12/2022 UNDER THE |
| LISTING OF PROJECT DATA LIST THIS AS A LEVEL 1 |
| ALTERATION. PLEASE REVIEW THE SCOPING FOR LEVEL 2 |
| ALTERATIONS SECTION 504.1 2020 FBC EXISTING BUILDING |
| CODE. THE RECONFIGURATION OR SPACE, THE ADDITION OR |
| ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION |
| OR EXTENSION OF ANY SYSTEM OR THE INSTALLATION OF ANY |
| ADDITIONAL EQUIPMENT, LEVEL 2. |
| |
| 2B) 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL |
| NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 3) COVERSHEET SUBMITTAL DATE 7/12/22/ SMOKE ALARMS |
| 703.2 IS FOR LEVEL 1. THIS IS A LEVEL 2 ALTERATION AND |
| THE FIRE ALARMS NEED TO SHOW COMPLIANCE WITH THE 2020 |
| FBC-EXIST. CODE SECTION 804.4.1.6.AS REQUIRED BY THE |
| FLORIDA FIRE PREVENTION CODE FOR EXISTING GROUP R-2. |
| |
| 4) SHEET A-1: |
| 4A) THE 1ST FLOOR PLAN SHOWS THE END UNIT TO BE |
| ACCESSIBLE, IT IS NOT CLEAR IF THE INTERIOR FLOOR LEVEL |
| IS THE SAME HEIGHT AS THE CONCRETE SLAB ON THE EXTERIOR |
| OR WITHIN ? INCH OF THE SAME HEIGHT. 2020 FBC-ACCESS. |
| CODE CHANGES IN LEVEL 303.2 AND 303.3. WHERE CHANGES IN |
| LEVEL ARE PERMITTED IN THE FLOOR OR GROUND SURFACES, |
| THEY SHALL COMPLY WITH SECTION 303. SEE 303.1 & 303.2. |
| |
| 4B) THE FLOOR PLAN OF THE ACCESSIBLE UNIT NEEDS TO SHOW |
| A ELEVATION VIEW. THE KITCHEN SINK SHOWS A FORWARD |
| APPROACH BUT NOT GOING UNDER THE SINK CABINET, A SIDE |
| APPROACH DOES NOT WORK SINCE THE SINK IS AGAINST THE |
| WALL. 2020 ACCESS CODE 606.2 CLEAR FLOOR SPACE. 606.5 |
| EXPOSED PIPES AND SURFACES. 606.3 HEIGHT. LAVATORIES |
| AND SINKS SHALL BE INSTALLED WITH THE FRONT OF THE |
| HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 4C) PLEASE PROVIDE ELEVATION VIEWS OF THE ACCESSIBLE |
| RESTROOM TO SHOW COMPLIANCE WITH PLUMBING ELEMENTS AND |
| ACCESSORIES, 2020 FBC-ACCESSIBILITY CODE CHAPTER 6. |
| |
| 5) SHEET A-2 SHOWS THE NEW GUARDRAIL / HANDRAIL SYSTEM |
| AT 36 INCHES. 2020 EXISTING BUILDING CODE. 801.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE 2020 FLORIDA BUILDING CODE, BUILDING. PLEASE |
| REVIEW SECTION 1014.2 FOR THE HEIGHT REQUIREMENTS. |
| PLEASE ALSO REVIEW SECTION 1014.16 HANDRAIL EXTENSIONS, |
| PLEASE SHOW THE FULL LENGTH OF THE HANDRAIL, GUARDRAIL |
| ASSEMBLY. |
| |
| 6) SHEET A-2 SHOWS THE NEW GUARDRAIL / HANDRAIL SYSTEM |
| AT 36 INCHES. 2020 EXISTING BUILDING CODE. 801.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE 2020 FLORIDA BUILDING CODE, BUILDING. 2020 |
| FBC-BUILD. CODE SECTION 1015.3 GUARDS SHALL NOT BE LESS |
| THAN 42 INCHES IN HEIGHT HIGH MEASURED VERTICALLY FROM |
| ON STAIRWAYS FROM THE LINE CONNECTING THE LEADING EDGE |
| OF THE TREAD NOSING. |
| |
| 7) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION.22061353 |
| |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ SEMI-RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |