2022-07-18 09:56:01 | FIRE REVIEW COMMENTS: | | THE FIRE PUMP SUPPORTING DOCUMENTS ARE NOT PART OF THIS | | APPROVAL. | | ALL JOINTS SHALL BE INSPECTED BY THE FIRE DEPARTMENT | | PRIOR TO COVERING. | | AT TIME OF INSPECTION, THE CONTRACTOR SHALL HAVE ON | | SITE THE MANUFACTURES SPECIFICATIONS FOR UNDERGROUND | | PIPING INCLUDING TORQUE REQUIREMENTS FOR BOLT | | ASSEMBLIES. | | C. WALKER | | 561-804-4762 | | [email protected] | | |
|