2022-07-26 11:07:11ON THE DRAWING SUBMITTED THE DETAIL SECTION 1/1 IS
 SHOWING THAT THE SUBDUCT, THE BATH EXHAUST FROM THE
 FLOOR BELOW, IS TO BE CLOSED WITH THE UL DESIGN. THIS
 SUBDUCT IS NOT TO BE CAPPED IN ANY WAY. REVISE THE
 DRAWING TO SHOW THE SUBDUCT TO BE OPEN.
  
 FMC 607.5.5 SHAFT ENCLOSURES. SHAFT ENCLOSURES THAT ARE
 PERMITTED TO BE PENETRATED BY DUCTS AND AIR TRANSFER
 OPENINGS SHALL BE PROTECTED WITH APPROVED FIRE AND
 SMOKE DAMPERS INSTALLED IN ACCORDANCE WITH THEIR
 LISTING.
 EXCEPTIONS:
 1. FIRE DAMPERS ARE NOT REQUIRED AT PENETRATIONS OF
 SHAFTS WHERE ANY OF THE FOLLOWING APPLY:
 1.1. STEEL EXHAUST SUBDUCTS EXTEND NOT LESS THAN 22
 INCHES (559 MM) VERTICALLY IN EXHAUST SHAFTS PROVIDED
 THAT THERE IS A CONTINUOUS AIRFLOW UPWARD TO THE
 OUTDOORS.