Plan Review Notes For Permit 22070050
Permit Number 22070050
Review Stop P
Sequence Number 2
Notes
Date Text
2022-10-26 13:05:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22070050 205 N DIXIE HWY
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 *PLEASE NOTE: IT APPEARS THAT POTENTIALLY UPDATED PLAN
 SHEETS A-108 AND A-109 ADDRESSING COMMENTS 2 THROUGH 5
 MAY HAVE NOT BEEN UPLOADED AS THE PLAN SHEETS ON FILE
 ARE FROM THE FIRST REVIEW CYCLE
 *PLEASE NOTE: UPDATED PLUMBING PLANS P-1 THROUGH P-5
 ARE ON FILE AND REVIEWED BUT OLDER P-1 THROUGH P-5 FROM
 FIRST REVIEW CYCLE ARE ON FILE AS WELL
  
 1) 1. SECOND REQUEST: PER FBC 1210.2.2, FBC PL 310.3,
 WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE PER FBC 1210.2.2. SECTION
 1210.2.2 STIPULATES THAT THE MATERIAL BE "HARD." THE
 INTENT OF THIS SECTION IS THAT THE SURROUNDING MATERIAL
 SHOULD NOT BE OF A TYPE THAT IS EASILY DAMAGED SUCH
 THAT THE MATERIAL COULD BECOME ABSORBENT AND THUS, NOT
 READILY CLEANABLE AND SANITIZED. PAINTED DRYWALL, EVEN
 WHERE COATED WITH HIGHLY DURABLE PAINTS SUCH AS EPOXY,
 DOES NOT MEET THE INTENT OF SECTION 1210.2.2. THE
 TYPICAL MATERIALS USED FOR THIS APPLICATION ARE CERAMIC
 TILE, FIBERGLASS REINFORCED PLASTIC (FRP) PANELS,
 PHENOLIC PANELS, LAMINATED PLASTIC PANELS, PAINTED
 STEEL AND STAINLESS STEEL.
 HARVARD JOLLY RESPONSE: THE WALLS ARE COATED WITH AN
 EPOXY TYPE COATING THAT PROVIDES A TILE-LIKE FINISH.
 IT HAS BEEN THE POSITION TAKEN BY THIS DEPARTMENT THAT
 PAINTED DRYWALL, EVEN WHERE COATED WITH HIGHLY DURABLE
 PAINTS SUCH AS EPOXY, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
  
 2) 2. SECOND REQUEST: THE WATER CLOSET SHALL BE
 POSITIONED WITH A WALL OR PARTITION TO THE REAR AND TO
 ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL BE
 16 INCHES NOT 15 INCHES MINIMUM TO 18 INCHES MAXIMUM
 FROM THE SIDE WALL OR PARTITION PER FBC ACC 604.2
 HARVARD JOLLY RESPONSE: SEE RESTROOM ELEVATIONS ON
 SHEET A-108.
 PLAN SHEET A-108 STILL SHOWS A MINIMUM 15 INCHES FROM
 SIDE WALL TO CENTER
  
 3) 3. SECOND REQUEST: THE SIDE WALL GRAB BAR SHALL BE
 42 INCHES LONG MINIMUM, LOCATED 12 INCHES (305 MM)
 MAXIMUM FROM THE REAR WALL AND EXTENDING A MINIMUM OF
 54 INCHES TOTAL FROM THE REAR WALL PER FBC ACC 604.5.1
 HARVARD JOLLY RESPONSE: SEE RESTROOM ELEVATIONS ON
 SHEET A-108.
 DETAIL DOES NOT SHOW MAXIMUM 54 INCHES TOTAL. THIS IS
 IMPORTANT BECAUSE DUE TO THE 12 INCHES MAXIMUM VERBIAGE
 USED IN THE CODE, A 42 INCH LONG GRAB BAR WOULD NOT
 PROVIDE 54 INCHES MINIMUM IF THE SPACE FROM THE REAR
 WALL WAS LESS THAN 12 INCHES.
  
 4) 4. RESTROOM ELEVATION ACKNOWLEDGED
  
 5) 5. SECOND REQUEST: PER FBC ACC 602.2, PROVIDE A
 CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 FOR THE
 MULTI-PURPOSE ROOM SINK.
 HARVARD JOLLY RESPONSE: SEE CABINET DETAIL 11/A-109.
 CABINET DETAIL 11/A-109 PROVIDES A CABINET ELEVATION
 BUT DOES NOT PROVIDE A CLEAR FLOOR SPACE
  
 6) 8. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE
 ELEVATION DETAIL FOR DRINKING FOUNTAIN(S). SHOW
 COMPLIANCE WITH FBC ACC 306 KNEE AND TOE CLEARANCE,
 602.4 SPOUT HEIGHT AND 602.7 SPOUT HEIGHT FOR STANDING
 PERSONS.
 JLRD RESPONSE: THE COOLER SPECIFIED IS AN ADA WATER
 COOLER WITH BOTTLE FILLER TYPE.
 IT IS ACKNOWLEDGED THE SPECIFIED COOLER IS ADA
 COMPLIANT. RESPECTFULLY, THE REQUEST IS FOR AN
 ELEVATION DETAIL FOR THE INSTALLATION AS IT IS ONLY
 COMPLIANT IF INSTALLED TO COMPLY WITH FBC ACC 306 KNEE
 AND TOE CLEARANCE, 602.4 SPOUT HEIGHT AND 602.7 SPOUT
 HEIGHT FOR STANDING PERSONS.
  
 7) 9. JLRD RESPONSE: THE APPROVED SHOP DRAWINGS FOR
 EACH OF THE ITEMS REQUESTED WILL SUBMITTED BY THE
 CONTRACTOR
 NEW COMMENT: PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1,
 PROVIDE AS A DEFERRED SUBMITTAL MANUFACTURER???S
 SPECIFICATION AND INSTALLATION GUIDES FOR THE EMERGENCY
 SHOWER/EYEWASH, DRINKING FOUNTAIN(S) AND THE WATER
 HEATER. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS SHALL BE SUBMITTED,
 APPROVED AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED
 AT YOUR OWN RISK.
  
 8) 16. SECOND REQUEST: EWH-1: PER WPB FBC 107.2.1
 PROVIDE COLD WATER WITH SHUT-OFF VALVE TO EWH-1 WATER
 HEATER AND PROVIDE INSTALLATION DETAIL. FBC PL 503.1
 DETAIL IS PROVIDED BUT NO VALVE IS SHOWN; TO BE CLEAR,
 AN ACCESSIBLE, DEDICATED SHUT OFF VALVE FOR THE WATER
 HEATER IS REQUIRED.
  
 9) 17. SLAB REPAIR DETAIL ACKNOWLEDGED
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  