Plan Review Notes
Plan Review Notes For Permit 22070050
Permit Number 22070050
Review Stop P
Sequence Number 1
Notes
Date Text
2022-08-11 15:16:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22070050 205 N DIXIE HWY
  
 1ST REVIEW
 PLUMBING COMMENTS:
  
 1. PER FBC 1210.2.2, FBC PL 310.3, WALLS AND PARTITIONS
 WITHIN 2 FEET OF SERVICE SINKS, URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT
 SURFACE PER FBC 1210.2.2. SECTION 1210.2.2 STIPULATES
 THAT THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION
 IS THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A
 TYPE THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL
 COULD BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE
 AND SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS SUCH AS EPOXY, DOES NOT MEET THE
 INTENT OF SECTION 1210.2.2. THE TYPICAL MATERIALS USED
 FOR THIS APPLICATION ARE CERAMIC TILE, FIBERGLASS
 REINFORCED PLASTIC (FRP) PANELS, PHENOLIC PANELS,
 LAMINATED PLASTIC PANELS, PAINTED STEEL AND STAINLESS
 STEEL.
  
 2. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES NOT 15 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION PER FBC ACC 604.2
  
 3. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING A MINIMUM OF 54 INCHES TOTAL
 FROM THE REAR WALL PER FBC ACC 604.5.1
  
 4. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
  
 5. PER FBC ACC 602.2, PROVIDE A CLEAR FLOOR OR GROUND
 SPACE COMPLYING WITH 305 FOR THE MULTI-PURPOSE ROOM
 SINK.
  
 6. PER FBC 606.5 WATER SUPPLY & DRAINPIPES UNDER
 LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED TO PROTECT AGAINST CONTACT.
  
 7. PER FBC ACC 602.1, PROVIDE PROVISION FOR DRINKING
 FOUNTAINS TO COMPLY WITH FBC ACC 307.1 PROTRUDING
 OBJECTS, 307.2 PROTRUSION LIMITS.
  
 8. PER WPB FBC 107.2.1, PROVIDE ELEVATION DETAIL FOR
 DRINKING FOUNTAIN(S). SHOW COMPLIANCE WITH FBC ACC 306
 KNEE AND TOE CLEARANCE, 602.4 SPOUT HEIGHT AND 602.7
 SPOUT HEIGHT FOR STANDING PERSONS.
  
 9. MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR
 THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING:
 ***A)EMERGENCY SHOWER/EYEWASH
 ***B) DRINKING FOUNTAIN(S)
 ***C) WATER HEATER
  
 10. PER WPB FBC 107.2.1, PLEASE PROVIDE NOTE "REFER TO
 MAIN COUNTY COURTHOUSE (MCCH) CENTRALIZED MAILROOM
 PROJECT MANUAL DIVISION 22 FOR PLUMBING
 SPECIFICATIONS".
  
 13. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL
 BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND
 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS
 STATING THE SAME.
  
 14. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 15. PROVIDE ENERGY EFFICIENCY FOR WATER HEATER; COMPLY
 WITH FBC EC TABLE C404.2
  
 16. EWH-1: PER WPB FBC 107.2.1 PROVIDE COLD WATER WITH
 SHUT-OFF VALVE TO EWH-1 WATER HEATER AND PROVIDE
 INSTALLATION DETAIL
  
 17. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL
 ON THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 18. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE
 CALCULATIONS FOR SIZING OF WATER DISTRIBUTION.
  
 19. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE
 CALCULATIONS FOR SIZING OF SANITARY PIPING.
  
 20. P-2 SANITARY FLOOR PLAN SHOWS A FLOOR DRAIN IN THE
 MEN'S RESTROOM; P-4 SANITARY RISER DOES NOT. PER WPB
 FBC 107.2.1, PLEASE CLARIFY AND RECONCILE PLANS.
  
 21. PER WPB FBC 107.2.1, PLEASE SHOW WATER LINE FROM
 TRAP PRIMER FOR FLOOR DRAINS IN THE MEN'S AND WOMEN'S
 RESTROOMS ON P-2 AND P-4.
  
 22. PER WPB FBC 107.2.1, PROVIDE DETAIL(S) FOR TRAP
 PRIMERS TO FLOOR DRAINS.
  
 23. PER WPB FBC 107.2.1 AND FBC PL 604.9 PROVIDE NOTE
 AT P-1/PLUMBING NOTE 10 AND P-5/TYPICAL WHA LOCATION
 DETAIL "WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE
 1010".
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS