2022-08-11 15:16:53 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 22070050 205 N DIXIE HWY |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: |
| |
| 1. PER FBC 1210.2.2, FBC PL 310.3, WALLS AND PARTITIONS |
| WITHIN 2 FEET OF SERVICE SINKS, URINALS AND WATER |
| CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT |
| SURFACE PER FBC 1210.2.2. SECTION 1210.2.2 STIPULATES |
| THAT THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION |
| IS THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A |
| TYPE THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL |
| COULD BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE |
| AND SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH |
| HIGHLY DURABLE PAINTS SUCH AS EPOXY, DOES NOT MEET THE |
| INTENT OF SECTION 1210.2.2. THE TYPICAL MATERIALS USED |
| FOR THIS APPLICATION ARE CERAMIC TILE, FIBERGLASS |
| REINFORCED PLASTIC (FRP) PANELS, PHENOLIC PANELS, |
| LAMINATED PLASTIC PANELS, PAINTED STEEL AND STAINLESS |
| STEEL. |
| |
| 2. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| OF THE WATER CLOSET SHALL BE 16 INCHES NOT 15 INCHES |
| MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR |
| PARTITION PER FBC ACC 604.2 |
| |
| 3. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE |
| REAR WALL AND EXTENDING A MINIMUM OF 54 INCHES TOTAL |
| FROM THE REAR WALL PER FBC ACC 604.5.1 |
| |
| 4. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 |
| |
| 5. PER FBC ACC 602.2, PROVIDE A CLEAR FLOOR OR GROUND |
| SPACE COMPLYING WITH 305 FOR THE MULTI-PURPOSE ROOM |
| SINK. |
| |
| 6. PER FBC 606.5 WATER SUPPLY & DRAINPIPES UNDER |
| LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE |
| CONFIGURED TO PROTECT AGAINST CONTACT. |
| |
| 7. PER FBC ACC 602.1, PROVIDE PROVISION FOR DRINKING |
| FOUNTAINS TO COMPLY WITH FBC ACC 307.1 PROTRUDING |
| OBJECTS, 307.2 PROTRUSION LIMITS. |
| |
| 8. PER WPB FBC 107.2.1, PROVIDE ELEVATION DETAIL FOR |
| DRINKING FOUNTAIN(S). SHOW COMPLIANCE WITH FBC ACC 306 |
| KNEE AND TOE CLEARANCE, 602.4 SPOUT HEIGHT AND 602.7 |
| SPOUT HEIGHT FOR STANDING PERSONS. |
| |
| 9. MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR |
| THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING: |
| ***A)EMERGENCY SHOWER/EYEWASH |
| ***B) DRINKING FOUNTAIN(S) |
| ***C) WATER HEATER |
| |
| 10. PER WPB FBC 107.2.1, PLEASE PROVIDE NOTE "REFER TO |
| MAIN COUNTY COURTHOUSE (MCCH) CENTRALIZED MAILROOM |
| PROJECT MANUAL DIVISION 22 FOR PLUMBING |
| SPECIFICATIONS". |
| |
| 13. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL |
| BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND |
| 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS |
| STATING THE SAME. |
| |
| 14. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL |
| WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE |
| SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| |
| 15. PROVIDE ENERGY EFFICIENCY FOR WATER HEATER; COMPLY |
| WITH FBC EC TABLE C404.2 |
| |
| 16. EWH-1: PER WPB FBC 107.2.1 PROVIDE COLD WATER WITH |
| SHUT-OFF VALVE TO EWH-1 WATER HEATER AND PROVIDE |
| INSTALLATION DETAIL |
| |
| 17. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL |
| ON THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM |
| THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW |
| SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT |
| AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR |
| SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS |
| WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED |
| SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| FOR FINAL INSPECTION. |
| |
| 18. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE |
| CALCULATIONS FOR SIZING OF WATER DISTRIBUTION. |
| |
| 19. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE |
| CALCULATIONS FOR SIZING OF SANITARY PIPING. |
| |
| 20. P-2 SANITARY FLOOR PLAN SHOWS A FLOOR DRAIN IN THE |
| MEN'S RESTROOM; P-4 SANITARY RISER DOES NOT. PER WPB |
| FBC 107.2.1, PLEASE CLARIFY AND RECONCILE PLANS. |
| |
| 21. PER WPB FBC 107.2.1, PLEASE SHOW WATER LINE FROM |
| TRAP PRIMER FOR FLOOR DRAINS IN THE MEN'S AND WOMEN'S |
| RESTROOMS ON P-2 AND P-4. |
| |
| 22. PER WPB FBC 107.2.1, PROVIDE DETAIL(S) FOR TRAP |
| PRIMERS TO FLOOR DRAINS. |
| |
| 23. PER WPB FBC 107.2.1 AND FBC PL 604.9 PROVIDE NOTE |
| AT P-1/PLUMBING NOTE 10 AND P-5/TYPICAL WHA LOCATION |
| DETAIL "WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE |
| 1010". |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER PX928 |
| PLUMBING INSPECTOR BN2148 |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-246-0882 |
| PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| THURSDAYS |