| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO. |
| 17-1003.04 SYSTEM TYPE E (16) MAXIMUM DESIGN PRESSURE |
| -105 PSF. DO NOT MEET THE MINIMUM ZONE 3 DESIGN |
| PRESSURE REQUIREMENT OF -108.17 FOR EXPOSURE CATEGORY C |
| AREAS. GENERAL LIMITATION #9 IS SPECIFICALLY REFERRED |
| TO IN THIS NOA. THE MAXIMUM DESIGNED PRESSURE |
| LIMITATION LISTED SHALL BE APPLICABLE TO ALL ROOF |
| PRESSURE ZONES (I.E. FIELD, PERIMETERS, AND CORNERS). |
| NEITHER RATIONAL ANALYSIS, NOR EXTRAPOLATION SHALL BE |
| PERMITTED FOR ENHANCED FASTENING AT ENHANCED PRESSURE |
| ZONES (I.E. PERIMETERS, EXTENDED CORNERS AND CORNERS). |
| THIS SYSTEM CAN?T BE USED. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |