2022-07-26 12:55:13 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| PERMIT- 22061699 |
| 7/26/2022 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P6: PROVIDE TDH CALCULATIONS- SECS. 4.4.9, |
| 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 & R4501.7.3 FBC |
| RES. |
| |
| 2) SHEET P6: PROVIDE THE PUMP CURVE ON THE SHEET MARKED |
| UP TO SHOW THE TDH AND FLOW RATE OF THE SYSTEM- SECS. |
| 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 & R4501.7.3 |
| FBC RES. |
| |
| 3) P6: PROVIDE A HYDROSTATIC RELIEF DEVICE AND SHOW THE |
| INSTALLATION LOCATION- SEC. R4501.21.4 FBC RES. |
| |
| 4) P6: LIST THE MAKE AND MODEL THE ANTI- ENTRAPMENT |
| SUCTION OUTLET COVERS AND DRAIN ASSEMBLIES AND SUBMIT |
| MANUFACTURER?S SPECIFICATIONS- SEC. R4501.6.6 FBC RES. |
| |
| 5) P6: PLEASE CLARIFY THE PURPOSE OF THE ?-INCH PEX |
| WATER SUPPLY PIPE. IS THE PIPE CONNECTED TO AN AUTOFILL |
| FOR THE POOL? PLEASE NOTE ON THE PLAN IF APPLICABLE AND |
| SHOW THE PEX LINE CONNECTION LOCATION TO THE WATER |
| SOURCE- SEC. 107.2.1 WPB. PLEASE NOTE A PVB BACKFLOW |
| PREVENTER IS REQUIRED AT THE AUTOFILL. PLEASE PROVIDE |
| NOTES ON THE PLAN INCLUDING THE MAKE AND MODEL OF THE |
| BACKFLOW PREVENTER- SECS. P2902.3 & P2902.5.4.1 FBC |
| RES. |
| |
| 6) P6: BACKFLOW PREVENTION IS REQUIRED FOR THE WATER |
| SERVICE IN ACCORDANCE WITH SECS. C, D, & E WPB |
| UTILITIES CROSS CONNECTION MANUAL. A SEPARATE PERMIT IS |
| REQUIRED FOR INSTALLATION OF THE DEVICE. PLEASE PLACE A |
| NOTE ON THE PLAN. |
| |
| 7) P6: PROVIDE A LIST OF CODES AND CONFORMANCE |
| STANDARDS USED IN THE DESIGN OF THE POOL- REFER TO SEC. |
| R4501.6.1 FBC RES. |
| |
| 8) P6: THE CODE SECTION NUMBERS LISTED UNDER THE NOTES |
| ARE NOT CORRECT OR CONSISTENT WITH CHAPTER 45 OF THE |
| FBC RES. PLEASE CORRECT THE NOTES- SEC. 107.2.1 WPB. |
| |
| 9) P6: THE PLANS SHALL BEAR THE PRINTED NAME AND |
| SIGNATURE OF THE DESIGNER OF RECORD- SEC. 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |