2022-09-02 10:43:25 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. |
| |
| 2) ON PAGE 5 OF THE PLANS, A 1' LAP OF THE #4 REBAR IS |
| SPECIFIED. FBC 2107.2.1 REQUIRES THE LAP TO BE 40 BAR |
| DIAMETERS. |
| |
| 3) SPECIFY THE TYPE OF CONCRETE BLOCK THAT WILL BE |
| USED. THE PLANS SHOW THAT THE CONCRETE BLOCKS ONLY HAVE |
| VERTICAL STEEL REINFORCING. NO HORIZONTAL REINFORCING |
| IS SPECIFIED. PROVIDE CALCULATIONS TO SHOW THAT THE |
| BLOCK CAN WITHSTAND THE LATERAL FORCES OF THE WATER AND |
| SOIL. FBC 107.2.1 |
| |
| 4) THERE IS NO EMPIRICAL DESIGN FOR MASONRY SWIMMING |
| POOLS. SUBMIT SIGNED AND SEALED ENGINEERING FOR THE |
| MASONRY PORTIONS OF THE POOL. FBC-R606.1 GENERAL |
| MASONRY CONSTRUCTION SHALL BE DESIGNED AND CONSTRUCTED |
| IN ACCORDANCE WITH THE PROVISIONS OF THIS SECTION AND |
| SECTION R301.2.1.1, TMS 402, TMS 403 OR TMS 404. |
| FBC-R606.1.1 PROFESSIONAL REGISTRATION NOT REQUIRED |
| WHEN THE EMPIRICAL DESIGN PROVISIONS OF APPENDIX A OF |
| TMS 402, THE PROVISIONS OF TMS 403, OR THE PROVISIONS |
| OF THIS SECTION ARE USED TO DESIGN MASONRY, PROJECT |
| DRAWINGS, TYPICAL DETAILS AND SPECIFICATIONS ARE NOT |
| REQUIRED TO BEAR THE SEAL OF THE ARCHITECT OR ENGINEER |
| RESPONSIBLE FOR DESIGN, UNLESS OTHERWISE REQUIRED BY |
| THE STATE LAW OF THE JURISDICTION HAVING AUTHORITY. |
| |
| 5) SPECIFY THE REQUIRED SPACING OF THE VERTICAL AND |
| HORIZONTAL STEEL REINFORCING IN THE POURED CONCRETE |
| WALLS AND THE SPACING IN EACH DIRECTION IN THE POOL |
| FLOOR. FBC 107.2.1 |
| |
| 6) INGROUND SWIMMING POOLS ARE REQUIRED TO COMPLY WITH |
| ANSI/APSP/ICC5. |
| A) SECTION 4.1 REQUIRES STRUCTURAL DESIGN AND MATERIALS |
| USED SHALL BE IN ACCORDANCE WITH ACCEPTED STRUCTURAL |
| ENGINEERING PRACTICES AND METHODS. |
| B) SHOW COMPLIANCE WITH SECTION 5.5 FOR THE SLOPE OF |
| THE POOL FLOOR. |
| |
| 7) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON |
| THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS |
| MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED. |
| PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH OF |
| THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |
| |