2022-07-07 17:19:18 | 1ST REVIEW FBC-2020 RES. PLUMBING | | PERMIT- 22061676 | | 7/7/2022 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET P1.0: PLEASE NOTE THAT SEPARATE PERMITS AND | | PLANS ARE REQUIRED TO RELOCATE THE POOL EQUIPMENT, AND | | FOR MODIFICATIONS TO THE IRRIGATION SYSTEM- SEC. 105.1 | | & 107.2.1 WPB. | | | | 2) P1.0 SANITARY RISER: PLEASE PROVIDE A VENT FOR THE | | BAR SINK FIXTURE DRAIN- SEC. P3101.2.1 FBC RES. | | | | 3) P1.0 SANITARY RISER: THE WET VENT FOR BATH NO.4 IS | | NOT IN COMPLIANCE WITH SEC. P3108.2.1 FBC RES- NOT MORE | | THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE | | UPSTREAM OF THE DRY VENTED FIXTURE DRAIN CONNECTION. | | | | 4) P2.0 SANITARY RISER: THE WET VENTS FOR BATH NO. 1 & | | NO. 2 ARE NOT IN COMPLIANCE WITH SEC. P3108.2.1 FBC | | RES- NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN SHALL | | DISCHARGE UPSTREAM OF THE DRY VENTED FIXTURE DRAIN | | CONNECTION. | | | | 5) P2.0 SANITARY RISER: A DRY VENT IS REQUIRED FOR BATH | | NO. 3 HORIZONTAL WET VENT- SEC. P3108.1 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|