2022-07-07 17:19:181ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22061676
 7/7/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1.0: PLEASE NOTE THAT SEPARATE PERMITS AND
 PLANS ARE REQUIRED TO RELOCATE THE POOL EQUIPMENT, AND
 FOR MODIFICATIONS TO THE IRRIGATION SYSTEM- SEC. 105.1
 & 107.2.1 WPB.
  
 2) P1.0 SANITARY RISER: PLEASE PROVIDE A VENT FOR THE
 BAR SINK FIXTURE DRAIN- SEC. P3101.2.1 FBC RES.
  
 3) P1.0 SANITARY RISER: THE WET VENT FOR BATH NO.4 IS
 NOT IN COMPLIANCE WITH SEC. P3108.2.1 FBC RES- NOT MORE
 THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE
 UPSTREAM OF THE DRY VENTED FIXTURE DRAIN CONNECTION.
  
 4) P2.0 SANITARY RISER: THE WET VENTS FOR BATH NO. 1 &
 NO. 2 ARE NOT IN COMPLIANCE WITH SEC. P3108.2.1 FBC
 RES- NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN SHALL
 DISCHARGE UPSTREAM OF THE DRY VENTED FIXTURE DRAIN
 CONNECTION.
  
 5) P2.0 SANITARY RISER: A DRY VENT IS REQUIRED FOR BATH
 NO. 3 HORIZONTAL WET VENT- SEC. P3108.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  