2022-07-07 17:32:17 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| PERMIT- 22061676 |
| 7/7/2022 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. REVIEW THE FOLLOWING |
| COMMENTS AND NOTE THAT GAS CAN BE UNDER A SEPARATE |
| PERMIT IF REQUESTED. |
| |
| 1) PROVIDE GAS PLANS INCLUDING A RISER DRAWING, |
| COMBUSTION AIR AND VENTING PLANS, AND SUBMIT |
| MANUFACTURER'S SPECIFICATIONS FOR ALL NEW GAS-FIRED |
| APPLIANCES. PLEASE NOTE THAT SEPARATE PERMITS ARE |
| REQUIRED FOR THE GENERATOR AND POOL HEATER- SEC. |
| 107.2.1 & 107.3.5.3 WPB. |
| |
| 2) REFER TO FBC RES. FUEL GAS CHAPTER 24 AND SECTION |
| 107.3.5.3 WPB - PROVIDE A COMPLETE CODE COMPLIANT RISER |
| DRAWING WITH THE FOLLOWING INFORMATION: |
| A) DELIVERY PRESSURE AT THE METER. |
| B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| C) TYPES AND SIZES OF PIPING. |
| D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| F) LOCATIONS OF REGULATORS, SHUTOFF VALVES, DRIP LEGS, |
| AND PIPE UNIONS. |
| G) OUTLET PRESSURES AT REGULATORS. |
| H) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| I) PIPE SIZING TABLES |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |