2022-08-02 17:41:24 | ROOFING REVIEW: |
| |
| 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| A)FLAT ROOF NOA 22-0107.02 SUBMITTED: SELECTED ASSEMBLY |
| ON PAGE 17 OF 18 DOESN'T MEET THE DESIGN PRESSURES FOR |
| ALL ROOF ZONES. PROVIDE SIGNED AND SEALED RAS 117 |
| CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER |
| AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE |
| OF NOA. NEED THE CALCULATIONS TO MEET THE DESIGN |
| PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| B)ROOF TILE NOA 21-1215.06 SUBMITTED. CLEARLY MARK |
| ADHESIVE PADDY SIZE TO BE USED AS REQUIRED BY CITY |
| POLICY FOR ALL ROOFING PERMITS TO VERIFY COMPLIANCE |
| WITH THE DESIGN PRESSURES OF SEC R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| C)ROOF TILE ADHESIVE SELECTED ON ROOF TILE NOA. |
| |
| 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| NOTE: PRODUCT APPROVAL LETTER WAS NOT SIGNED BY THE |
| ARCHITECT REVIEWING THE PRODUCT APPROVALS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |