Plan Review Notes
Plan Review Notes For Permit 22061673
Permit Number 22061673
Review Stop P
Sequence Number 1
Notes
Date Text
2022-07-13 08:19:561ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22061673
 7/13/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLANS SHOW TWO DWELLINGS ON THE SAME LOT WHICH
 WILL REQUIRE WATER USERS TO INSTALL A BACKFLOW
 PREVENTION ASSEMBLY AT THE POINT OF DELIVERY. A REDUCED
 PRESSURE ZONE BACKFLOW DEVICE WILL BE REQUIRED FOR THE
 WATER METER PER SECS. C, D, & E WEST PALM BEACH
 UTILITIES CROSS-CONNECTION MANUAL. PLEASE ADD THE MAKE
 AND MODEL OF THE DEVICE TO THE BACKFLOW PREVENTION
 DEVICE SCHEDULE ON SHEET P801, AND SUBMIT THE CIVIL
 PLANS REFERENCED IN THE SCHEDULE.
 PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  