2022-08-02 17:39:52RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22061673 365 PLYMOUTH RD
  
 1- LOT DRAINAGE
 PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE
 DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT
 WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING SECTIONS: R401.3 FBC-RESIDENTIAL. SEC.
 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 2-THE PROPOSED ENTRY DOOR DOESN'T COMPLY WITH THE
 EGRESS REQUIREMENTS. NEED TO PROVIDE SIDE HINGED DOOR.
 SEC. R311.1 AND SEC. R311.2 FBC-RESIDENTIAL. REVISE AS
 REQUIRED.
  
 3- REVISE ROOF SHEATHING NAILING SPECIFICATIONS TO
 COMPLY WITH NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS.
 REVISE NAIL TYPE, SIZE AND SPACING. NOTE: NEED TO USE
 RING SHANK NAILS. ROOF SHEATHING NEEDS TO BE NAILED AT
 4 INCHES O.C. IN THE FIELD AND EDGES AS REQUIRED BY
 SEC. R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR
 EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM
 REQUIREMENTS.
  
 4- SHEET A0.0:
 A) THE SQUARE FOOTAGE OF THE NEW CABANA STRUCTURE IS
 327 S.F. NOT 275 S.F. REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 B)PROJECT DATA IS INCORRECT. SCOPE OF WORK IS
 CONSTRUCTION OF A NEW RESIDENTIAL STRUCTURE. THE
 CORRECT CODE TO REFERENCE IS THE 2020 FBC-RESIDENTIAL
 NOT THE EXISTING BUILDING CODE. ALSO, THE CORRECT
 BUILDING CODE EDITION IS THE 7TH EDITION NOT THE 5TH
 EDITION. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS. CHAPTER 553 F.S.
  
 5- ROOF VENTILATION
 SPECIFY ROOF CROSS VENTILATION AS REQUIRED BY SEC. R806
 FBC-RESIDENTIAL. SPECIFY SIZE AND LOCATION.
 NOTE: IF DESIGNING UNVENTED ATTICS, THEN SPECIFY HOW
 COMPLYING WITH SEC. R806.5 FBC-RESIDENTIAL.
  
 6- SHEET S3.1:
 A) ROOF AND WALLS DESIGN PRESSURES SPECIFIED ON THE
 COMPONENTS AND CLADDING ALLOWABLE WIND PRESSURES TABLES
 ARE TOO LOW FOR EXPOSURE "C".
 TABLE R301.2(2) FBC-RESIDENTIAL AND TABLE R301.2(3)
 FBC-RESIDENTIAL.
 REVISE AS REQUIRED OR PROVIDE ACTUAL CALCULATIONS. SEC.
 107.2.1.2 CITY AMENDMENTS.
 NOTE: KEEP IN MIND THERE ARE FLAT AND PITCHED ROOFS
 WHEN PROVIDING THE REVISED DESIGN PRESSURES.
  
 B) REVISE TABLE NOTES NOTE #1. THE MINIMUM DIMENSIONS
 FOR "A" IS 4'-0". SEE FOOTNOTE "A" ON FIGURE R301.2(7)
 FBC-RESIDENTIAL.
  
 7- CANOPY DETAILS/SPECIFICATIONS:
 A)MISSING THE CONNECTION OF THE 2X6 ROOF JOIST TO THE
 WALL LEDGER. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 B)WALL LEDGER IS MISSING HOW EMBEDMENT IS REQUIRED FOR
 THE ANCHOR SUPPORTING THE LEDGER. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 C) MISSING SPECIFICATIONS FOR 3X KICKER BRACE. SPECIFY
 STRUCTURAL MEMBER SIZE AND FASTENING TO BEAM AND WALL.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 8- ROOF FRAMING PLAN IS MISSING THE DETAIL AND
 SPECIFICATIONS FOR THE STRUCTURAL LEDGERS
 (PERPENDICULAR AND PARALLEL TO THE 2X8 ROOF JOISTS).
 PROVIDE DETAIL/SPECS. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 9- ENERGY CALCULATIONS FORM R402-2020 SUBMITTED:
 A)CEILING INSULATION DOESN'T MATCH INSULATION R-VALUE
 SPECIFIED ON PLANS. FORM R402-2020 REQUIRES R-30 MIN.
 CEILING INSULATION. ALSO, MASONRY WALL INSULATION
 DOESN'T MATCH PLANS EITHER. NEED TO COORDINATE WITH
 ARCHITECT OR THIS FORM CAN NOT BE USED. ALSO, MASONRY
 WALL INSULATION DOESN'T MATCH PLANS EITHER. SECTION
 R101.5.1.1.1 FBC-RESIDENTIAL.
  
 B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. THE CONDITIONED FLOOR AREA IS INCORRECT. ADDRESS
 ZIP IS INCORRECT. PERMIT TYPE IS INCORRECT. THIS IS NEW
 CONSTRUCTION NOT RENOVATION/ADDITION. PROVIDE BUILDER'S
 NAME, PERMITTING OFFICE, JURISDICTION NUMBER (604700).
 SECTION R101.5.1.1.1 FBC-RESIDENTIAL.
  
 C) REVISE MANDATORY REQUIREMENTS. WHY AIR LEAKAGE AND
 WATER HEATERS ARE MARKED N/A?. THEY ARE MANDATORY.
 SECTION R101.5.1.1.2 FBC-RESIDENTIAL.
  
 10- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)FLAT ROOF NOA 22-0107.02 SUBMITTED: SELECTED ASSEMBLY
 ON PAGE 17 OF 18 DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES. PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE
 OF NOA. NEED THE CALCULATIONS TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL.
  
 B)ROOF TILE NOA 21-1215.06 SUBMITTED. CLEARLY MARK
 ADHESIVE PADDY SIZE TO BE USED AS REQUIRED BY CITY
 POLICY FOR ALL ROOFING PERMITS TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC R301.2.1
 FBC-RESIDENTIAL.
  
 C)ROOF TILE ADHESIVE SELECTED ON ROOF TILE NOA.
  
 D)INSWING RESTROOM DOOR AS SHOWN ON PLANS.
  
 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: PRODUCT APPROVAL LETTER WAS NOT SIGNED BY THE
 ARCHITECT REVIEWING THE PRODUCT APPROVALS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,